Calibrating The Pressure Transducer - Waeco AirCon Service Center ASC5100G Instrucciones De Uso

Estacion de mantenimiento de aire acondicionado
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Service tasks
"Service completed" displays the amount of service work performed
using the air conditioning service unit since the last reset (see date).
9.3.1
Leak test
After changing the filter, perform a leak test with an approved testing
device.
9.4

Calibrating the pressure transducer

I
NOTE
The pressure transducer has to be correctly calibrated in order to make
accurate pressure measurements.
Calibration is required:
 Every four weeks
 If the AirConServiceCenter has been subjected to heavy shaking
 Every time the vacuum pump oil is changed
 If the display shows implausible pressure readings
1. In the basic menu, use the cursor keys  or  to select "Other
selections":
2. Depressurise the unit (as described in chapter "Changing the dryer
filter" on page 91).
3. Press ENTER to confirm.
4. Use the cursor keys  or  to select "Service":
5. Press ENTER to confirm.
6. Enter the password "2224".
7. Confirm "Pressure transducer" by pressing ENTER.
94
All manuals and user guides at all-guides.com
Service completed:
Number
STOP-EXIT
Short selection
Free selection
Other selections
ENTER-OK
Service.
ENTER-OK STOP-EXIT
ASC5100G
08/03/17
4
EN

Publicidad

Tabla de contenido
loading

Tabla de contenido