2000Ω and repeat the test.
NOTE: do not connect the device to voltages higher than 500 VAC rms.
5. SPECIFICATIONS
Insulation resistance
Measuring Scales:
Measuring Scale:
Precision:
current::
Energy Consumption:
AC voltage
Scale:
Resolution:
Precision:
Line Frequency
Interval:
Continuity
Ohm Scale::
Resolution:
Precision:
Terminal voltage
Open circuit:
Terminal current
Open circuit:
Ohm Scale:
Resolution:
Precision:
KPS-MA10 • Isolation, voltage and continuity meter
200MΩ, testing voltages: 250V, 500V DC +/-
10%
Resolution: 1 account/100KΩ
2000MΩ, testing voltage: 1000V DC +/- 10%
Resolution: 1 account/1MΩ
+/-1,5% of reading +/-5 digits (200MΩ scale)
+/-3% of reading +/-3 digits (below 1 GΩ)
+/-5% of reading +/-5 digits (below 2 GΩ)Output
1 mA DC min. 0.25 MΩ (250V scale)
1 mA DC min. 0.5 MΩ (500V scale)
1 mA DC min. 1 MΩ (1,000V scale)
Max. Current Consumption approx. 250mA
0-500V
1V
+/- 1,5% of reading +/- 3 digits
40-120Hz
0-20Ω
0,01Ω
+/-1.5% of reading +/-5 digits
4 V DC min.
210 mA DC min.
0-2 KΩ
1Ω
+/- 1,5% of reading +/-3 digits
12