Tripp-Lite SmartOnline SU6000RT3U Manual Del Propietário página 15

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Manual Bypass Operation
The following procedure only applies to UPS system configurations that include a 6kVA or 10kVA transformer module. The procedure
details how to service or replace the power module while supplying equipment connected to the transformer module with utility power.
NOTE: since the power module and battery module will be disconnected during the procedure, they will be unable to supply battery backup
support to equipment connected to the transformer module in the event of a blackout.
WARNING! For qualified service personnel only. Failure to follow this procedure completely will not adequately power down the
UPS power module, resulting in the continued risk of death or injury from potential contact with high voltage.
1. Disable PowerAlert Software and disconnect communication cable from the power module's communication ports
2. Turn transformer module's Bypass Switch
3. Press power module's OFF Button
in the LCD panel
D
.
4. Turn off the transformer module's double-pole AC to UPS breaker
5. Turn off the power module's double-pole input breaker
6. Disconnect battery module cable from the power module's battery connector
7. FOR 10kVA POWER MODULES ONLY: Use a voltage meter to check the cable connecting the power module's terminal blocks
the transformer module's terminal blocks
cabling.
The power module is now safely powered down and maintenance/replacement can be performed.
G
F
A
H
6kVA Models (Rear Panel)
All manuals and user guides at all-guides.com
to "BYPASS".
B
, if power module is powered, until a beep is heard and a "BYPASS MODE" message is displayed
C
F
and double-pole output breaker
J
to ensure the power module is no longer powered. Once it is no longer powered, remove the
E
B
6kVA & 10kVA Models
(Front Panel)
(for power module maintenance or replacement)
.
E
G
H
.
G
A
I
10kVA Models (Rear Panel)
D
C
15
A
.
.
F
I
to
H
J
E
B

Publicidad

Tabla de contenido
loading

Tabla de contenido