Mounting (Tower)
Mount all modules in an upright, tower position using included base stands. The user must determine the fitness of hardware and procedures
before mounting.
1
The UPS system is shipped with two sets of plastic feet
can be used to tower mount the UPS's power module, a battery module and either an
isolation transformer module or a second battery module.
Adjust the feet to a width of 10.25 inches (26 cm) for a UPS power module and
battery module, or to a width of 15.375 inches (39 cm) for three units. Align the feet
in your installation area, approximately 10 inches (26 cm) apart. Have one or more
assistants help you place the units on their sides in the feet. The control panel of
the UPS should be the UPS's upper corner and face outward. If you are installing
a transformer module, place it between the UPS power module and its battery module.
Rotate the power module's Control Panel to view it easier while the UPS is tower
2
mounted. Insert a small screwdriver, or other tool, in the slots on either side of the
Control Panel. Pop the panel out; rotate it; and pop the panel back into place.