EN
Service
Troubleshooting
The list of faults/causes/possible solutions for a set of main failures is a guideline for professional personell authorised to carry out
service and maintenance. Irregular burner operation or malfunction: check that every adjustment parameter is correctly set as per
instruction on this manual.
The burner does not start.
-
Main switch in "0".
-
Fuses are blown.
-
Boiler thermostats are in open position.
-
Control box is defective.
The burner runs the prepurging but does not ignite and then switches into safety condition.
-
Control box is defective.
-
Ignition transformer is defective.
-
Electrodes are dirty.
-
Electrodes are defective.
-
Electrodes are in wrong position.
-
Nozzles are clogged.
-
Nozzles are too worn.
-
Filters are clogged.
-
Oil pressure too low.
-
Combustion air flow rate excessively high related to nozzle's flow rate.
The burner ignites but then switches into safety condition.
-
Control box is defective.
-
Nozzles are clogged.
-
Nozzles are too worn.
-
The photocell does not detect the flame.
-
Filters are clogged.
-
Oil pressure too low.
-
Combustion air flow rate excessively high related to nozzle's flow rate.
The burner does not switch to High flame.
-
1st(Low flame) and 2nd (High flame) stage manual switch on control board is in wrong position.
-
Control box is defective.
-
2nd (3rd) stage solenoid valve coil is defective.
-
Oil pressure too low.
-
Filters are clogged.
-
2nd (3rd) stage nozzle is too worn.
-
2nd (3rd) stage nozzle is clogged.
-
Air damper motor jack not properly adjusted or defective.
18
www.ecoflamburners.com