Descargar Imprimir esta página

Ecoflam MAIOR P 60 AB HS Serie Manual De Uso página 8

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 45
EN
Function
­ General safety functions
Description of functions
When the system is switched on for the
first time, after a power failure or safety
shutdown, after a lack of fuel or after the
system has been out of operation for 24
hours, the pre-ventilation period of 25
seconds begins.
During pre­purge period:
- blower pressure is monitored.
- the combustion chamber is monitored for
flame signals.
At the end of the pre­purge period:
- ignition is switched on.
- main and safety valve are opened.
- burner starts.
Monitoring
The flame is monitored by an
photoresistor. The burner switches to lock-
out if it doesn't survey the light of the
flame.
Safety functions
- If no flame is produced when the burner
is started, the burner will be switched off at
the end of the safety period, lasting no
more than 5 seconds, and the oil valve will
close.
- If the flame goes out during operation,
the oil supply is interrupted within one
second. A restart takes place. Once the
HS
105
8
www.ecoflam­burners.com
burner starts, operation is continued.
Otherwise, a safety lock-out occours.
- If there is a lack of air during
preventilation or operation, a safety lock-
out occours.
- If there is a lack of oil, the burner does
not begin operation or switches off.
In the event of controller shutdown
- Controller thermostat interrupts heat
request.
- Oil solenoid valves close.
- Flame goes out.
- Burner motor switches off.
- Burner is ready for operation.
101
103
M
M1
102
106
104
T1
118
Y2
Y1
101
Fan
M1
Air damper motor
T1
Ignition Transformer
Y1
Solenoid valve
Y2
Solenoid valve
HS
Hidraulic system
102
Oil pump
103
Air damper
104
Oil pressure regulator
105
Hoses
106
Filter
118
Nozzle
420010259503

Publicidad

loading