Transfer Critical Load From Maintenance Bypass To Line Mode - Tripp-Lite SmartOnline S3MX Manual Del Propietário

Ocultar thumbs Ver también para SmartOnline S3MX:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 71
7. UPS Operation

7.3.2 Transfer Critical Load from Maintenance Bypass to Line Mode

Turn ON the battery breaker (external battery cabinet).
Step 1
Step 2
Single input model:
Turn ON the Q1 Input 1 breaker.
Dual input model (Option):
Turn ON the Q1 Input breaker and Q2 Input breaker.
S3M120KXD (100 kVA/200 kVA) Models
Go to the LCD INFORMATION Menu. Choose "SYSTEM" to ensure that Bypass Mode is enabled ("Power By Bypass"). If
Step 3
Bypass Mode is disabled, set it to "enabled" through the SETUP menu and confirm the UPS is operating in Bypass Mode
before proceeding.
Step 4
Turn ON the Q3 Output breaker.
Q1
Input 1
S3M100KX
S3M120KX
(100 kVA/200 kVA) Models
Q1
Q2
Input 1
Input 2
S3M100KXD
00KVA/120KVA
Q3
Output
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100kVA/120kVA) Models
Single input model:
Turn ON the Q1 Input 1 breaker.
(160 kVA/200 kVA) Models
Dual input model (Option):
Turn ON the Q1 Input breaker and Q2 Input breaker
Q1
Input 1
S3M200KXD (160 kVA/200 kVA) Models
160KVA/200KVA
Turn ON the Q3 Output breaker.
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models
59
Q1
Input 1
S3M160KX
S3M200KX
Q2
Input 2
S3M160KXD
2018/01/01
Q3
Output

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido