4. Control Panel and LCD Operations
Table 4.9: Setup-Battery Setting List
Setting Item
Sub Item
Battery Capacity
--
in Ah
Maximum Charging
Recommended to Use 10%
Current
Battery Amp-Hour Rating
Low Voltage
Battery Low/
Low Capacity
Shutdown Setting
Shutdown Voltage (LVC)
Battery Test
Periodic Battery Test
Battery Test Interval
Stop by Time
Stop by Battery Voltage
Stop by Battery Capacity
Battery Age Alert
Battery Age Alert (Months)
Temperature
--
Compensation
Charging Voltage
--
Auto-Restart Battery
--
Voltage
Explanation
Set battery capacity. (up to 999)
• 9Ah (Default)
MUST be set after UPS installation or battery capacity is changed.
Set battery maximum charging current. (1~24A 100KVA/1~32A 120KVA/1~40A
160KVA/1~48A 200KVA)
• 2A (Default), may be increased via the display
MUST be set after UPS installation or battery capacity is changed.
Set battery low voltage. (10 ~11.5V) x (Battery Number)
• 11V x Battery Number (Default)
Set battery low capacity. (20~50%)
• 20% (Default)
Set battery voltage point for system shutdown in Battery Mode. (10.0V) x (Battery
Number)
• 10V x Battery Number (Default)
Set periodic battery test disable or enable.
• Disable (Default)
• Enable
Set battery test interval. (7~99 Days)
• 30 Days (Default)
Set testing time for battery test. (10~1000 Seconds)
• 10 sec (Default)
Set stop battery voltage in battery test. (11~12V) x (Battery Number)
• 11V x Battery Number (Default)
Set battery capacity to stop battery testing. (20~50%)
• 20% (Default)
Set battery age for replacement. (Disable, 12~60 Months)
• Disable (Default)
If this feature is enabled and the battery has been installed over this period, there
is a "Battery Age Alert" warning to indicate it.
Set battery temperature compensation.
• When Enabled, 3(mV/C/cell)
Set battery charging voltage. (2.30~2.35V)
• 14.1V/Battery, 2.35V/Cell (Default)
Set battery float voltage. (2.23~2.35V)
• 13.65V/Battery, 2.27V/Cell (Default)
Set auto-restart battery voltage. (0 or 12.0V~13.0V)
• 0V (Default)
34