The operation mode of the amperometric sensor is selected either the limit switch-
es are provided or not.
On: No limit switches. During the TSLD time, the activation of the amperometric
sensor is read by the control unit as limit switch and stops the motor.
During the TM time, the amperometric sensor is read by the control unit as obsta-
cle present and it DOES NOT stop the motor, but reserves the movement. There-
NOlS
fore, without limit switches the TM time must be lower than the total stroke time.
Note: To use this function, close the limit switch contacts with jumpers.
Off: Limit switches provided. The amperometric sensor activation is interpreted
by the control unit as obstacle present in the gate movement area. Similarly to the
safety edge activation, the control signal is sent to stop and reverse movement for
approx. 3s.
Service light function is enabled or disabled on output 9-10.
On: at each movement, the contact is closed for approx. 90s.
For the light control use the auxiliary relay (24Vdc/500Ω min) .
serL
Off: The output has the SCA function, open gate LED: open contact with closed
gate, flashing light during gate movement, closed contact with open gate.
See wire diagram.
Enables or disables the inversion stroke function
On: Function enabled. Before each opening or closing manoeuvre the control unit
ham
orders a manoeuvre of 2s in the opposite direction to facilitate the release of the
electric lock.
Off: Function disabled.
The second radio channel is enabled or disabled onto terminals 9/10.
On: 9/10 output preset as second radio channel.
2ch
The SERL logics must be set to OFF.
Off: 9/10 output can be set as SCA or service light.
MENU
Displays the number of complete cycles (open+close) carried out by the automation.
NMAN
When the <PG> button is pressed for the first time, it displays the first 4 figures, the second time it shows the
last 4. Example <PG> 0012
RESET of the control unit. ATTENTION!: Returns the control unit to the default values.
Pressing the <PG> button for the first time causes blinking of the letters RES, pressing the <PG> button again
RES
resets the control unit.
Note: The transmitter codes are not erased from the receiver.
The figure besides shows the trend of the gate speed (V
axis) when time changes (T axis).
The scheme is valid in both opening and closing phases,
for both motors.
If a (START) control is given, the door/gate leaf starts mov-
ing with a standard speed.
In this phase, the torque is adjusted according to PMO1/
PMO2 parameters for the opening phase, and PMC1/
PMC2 parameters for the closing phase.
The leaf then continues its stroke at standard speed for the
entire time preset by TM1/TM2 parameter.
Braking then starts for the duration preset by TSLD pa-
rameter.
Speed during braking is adjusted by SLDS parameter.
Before the TSLD time has elapsed, the leaf must reach the FC limit switch or the mechanical stop (amperometric sensor trigger-
ing).
To obtain a correct presetting of the parameter, proceed as follows:
Check that the NOLS logics is correctly set based on the presence or absence of limit switches.
With NOLS=OFF (limit switches are present):
1 Disable braking (SLD=OFF)
2 Totally open or close the door/gate, while measuring the time required for the operation.
3 Preset the value read on TM1/TM2 parameter, deducting the desired braking time (for example: with 25sec total opening and a 5
sec braking being required: preset TM1/TM2 on 20sec).
4 Preset the TSLD value at a value some seconds higher than braking (in our example: 10 sec).
5 Reactivate braking (SLD=ON)
6 Preset the PMO/PMC values, according to regulations in force.
FUNCTION
FUNCTION
>>> <PG> 3456: made 123.456 cycles.
GATE SPEED ADJUSTMENTS
V
MEMO
ON-OFF-(Default)
(OFF)
(OFF)
(OFF)
(OFF)
T
15