ENGLISH
Fresh air supply
The air used for combustion in any well-insulated house needs
to be replaced. This is particularly important in houses with
mechanical ventilation. Such replacement air can be procured
in several ways. The most important thing is to supply the air
to the room where the stove is placed. Place the outside wall
valve as close to the stove as possible and make sure that it
can be closed when the stove is not in use.
For the fresh air supply connection, follow the national and
local building regulations.
Closed combustion system
Use the stove's closed combustion system if you live in recently
built, airtight dwellings. Connect the external combustion air
through a ventilation pipe through the wall or the floor.
Air supply
The amount of combustion air for Jøtul's products is approximately
20-40 m 3 /h. The outside air connection may be fitted directly to
the Jøtul F 105 through:
•
the bottom
•
through a flexible supply hose from the outside/chimney
(only if the chimney has its own duct for external air) and to
the product's outside air connector.
Fig. 2A, through an outside wall
Fig. 2B, through the floor and ground plate
12
Fig. 2C, through the floor and basement
Fig. 2D, indirectly through an outside wall