1.1 humiSonic (UU0*R)

Range of ultrasonic adiabatic humidifi ers for direct humidifi cation in rooms,
with built-in fans for uniform atomised water distribution. humiSonic is
suitable for many applications, such as: the humidifi cation in production
plants, datacenters, warehouses, printing facilities, museums, restoration
workshops, theatres, etc., where optimisation of room humidity is essential
in ensuring personal comfort and safeguarding goods.

1.2 Part numbers

P/N
Description
UU0(X)R(*)0001 without auxiliary card, without humidity probe
UU0(X)R(*)AS01 with auxiliary card and with humidity probe
(X) = 2 à 2 kg/h (4.4 lbs/h), 4 à 4 kg/h (8.8 lbs/h), 6 à 6 kg/h (13.2 lbs/h),
8 à 8 kg/h (17.6 lbs/h)
(*) = D à power supply 230 Vac, 1 à power supply110 Vac

1.3 Dimensions and weights

317
Models
UU02
Production kg/h (lbs/h)
2 (4.4)
Width A mm (in)
Height mm (in)
Depth mm (in)
483 (19)
Weight kg (lb)
packaged
11 (24.2)
empty
9,5 (20.9) 12,5 (27.6) 15,5 (34.2) 18,5 (40.8)
installed*
10,3 (22.7) 14,1 (31.1) 17,9 (39.5) 21,7 (47.8)
* in operating conditions, fi lled with water.

1.4 Opening the packaging

□ Make sure the package is intact upon delivery and immediately notify
the transporter, in writing, of any damage that may be due to careless
or improper transport;
□ move the humidifi er to the site of installation before removing from
the packaging, grasping the neck from underneath;
□ open the cardboard box, remove the protective material and remove
the humidifi er,
□ the unit must be always stored in a dry place before installation.

1.5 Material supplied

Make sure the following are included:
1.
wall-mounting bracket;
2.
kit of screws and anchors;
3.
1 cable gland;
4.
4 feet;
5.
user manual.

1.6 Preparing for assembly

The unit is designed to be assembled on a horizontal support or wall
that can support its weight in normal operating conditions (see par.

"Wall-mounting");

1. INTRODUCTION AND ASSEMBLY

Tab. 1.a
Fig. 1.a
UU04
UU06
UU08
4 (8.8)
6 (13.2)
8 (17.6)
317 (12.5)
274 (10.8)
608 (24)
733 (28.9) 858 (33.8)
14 (30.9)
17 (37.5)
21 (46.3)
Tab. 1.b
Install the humidifi er in a safe place where it cannot be tampered with,
as far as possible from any air fl ows;
Position the humidifi er horizontally using a spirit level, observing the
minimum clearances in mm (see Fig. 1.b) to ensure the correct fl ow of
supply air and allow the required maintenance operations.
≥ 500
(19.7")
Note: the minimum distance at the rear is recommended for
assembly on a horizontal support.
Important: for installation on a horizontal support/wall:
Important:
1.
the humidifi er takes in air through by the slits at the back/bottom
respectively;
2.
the feet/spacers are fi tted at the bottom/rear;
3.
the fi ll/drain hoses are attached at the rear/on the bottom;
4.
the power cable gland is fi tted at the rear/on the bottom;
5.
remove the rear bracket for assembly on a horizontal support.
ASSEMBLY ON A HORIZONTAL SUPPORT
3
WALL-MOUNTING
2
1
AIR
1.7 Wall-mounting
ATTENTION: mount the unit only to a masonry wall
Fit the humidifi er to the wall using the support bracket already fi xed to
the humidifi er, and the kit of screws supplied (for the dimensions and
weights see the previous paragraph).
7
Direct version for room applic. +0300062IE - rel. 1.3 - 15.07.2019
≥ 450
(17.7")
≥ 200...300
(19.7")
≥ 500
(19.7")
<0,5°
Fig. 1.b
1
4
1
AIR
2
2
Fig. 1.c
3
2
1
4
AIR
Fig. 1.d
ENG
.