Alarms - Carel humiSonic Manual Del Usuario

Humidificadores por ultrasonidos
Ocultar thumbs Ver también para humiSonic:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ENG
red LED signal
code and
(*)
symbol
on display
(fl ashing)
2 fast fl ashes
Et
-
5 fast fl ashes
EP
3 fast fl ashes
EF
4 fast fl ashes
Ed
5 slow fl ashes
CL
6 fast fl ashes
PU
-
2 slow fl ashes
H^
3 slow fl ashes
H_
4 slow fl ashes
EE
1 fast fl ash
E0
7 slow fl ashes
OFL
8 fast fl ash
EL
6 slow fl ashes
ES1
ES2
ES3
1 slow fl ash
-bu
9 fast fl ashes
EtL
To reset the alarms, press ESC once to mute the buzzer, press ESC a
second time to completely reset the alarm.
(*) Fast fl ash: 0.2 seconds ON and 0.2 seconds OFF
Slow fl ash: 1 second ON and 1 second OFF
Direct version for room applic. +0300062IE - rel. 1.3 - 15.07.2019

9. ALARMS

meaning
cause
Autotest failed
- Fill not connected or
insuffi cient
- drain open
- faulty fl oat
No production
Malfunction of piezoelectric
transducers
No water
Interruption to water supply or
fi ll solenoid valve malfunction
No drain
Drain solenoid valve/circuit
malfunction
Tank maintenance
b5 operating hours for
request signal
recommended maintenance
exceeded
External control
Cable interrupted/
signal not
disconnected/not connected
connected correctly
correctly.
High humidity
The signal from the probe
indicates humidity above
80%rH
Low humidity
The signal from the probe
indicates humidity less than
20%rH
EEPROM alarm
Problems in the EEPROM
Functional test not
Functional test not performed
performed
by manufacturer/EEPROM
problems
Master Offl ine
Loss of connection from the
serial master (If D37=1)
Water level alarm
Level too high during atomised
water production due to:
fi ll SV leak
transducer malfunction
fan malfunction
Alarm on slave unit
Display slave unit from terminal
1/2/3
for details of the alarm
Backup unit not
The backup unit is off or has an
available
alarm: contact J17 on the main
unit is open
End of piezoelectric
The unit has reached AF
transducer life
working hours (default 9999 h)
solution
alarm relay
Check:
yes
water supply and
fi ll valve;
blockage of fi lter on
fi ll solenoid valve;
check drain
solenoid valve and
drain connection;
Carry out
yes
maintenance on tank
Check:
yes
water supply and
(in the 10
fi ll valve;
min. waiting
blockage of fi lter on
period)
fi ll solenoid valve
Check drain valve and
yes
drain connection
Carry out
no
maintenance on
tank and transducers
(cap. 9)
Check the reference
yes
signal (4 to 20 mA or 2
to 10V).
Check humidity probe
yes
signal/cable
Check humidity probe
yes
signal/cable
If the problem persists,
yes
contact the CAREL
service centre
If the problem persists,
yes
contact the CAREL
service centre
Check state of the
yes
Master / Cable
Check:
yes
fi ll SV
transducers
fans
see specifi c alarm
code, chapter
"Network connection"
Check the connection
from the alarm relay
on the backup unit to
input J17 on the main
unit.
Replace the
piezoelectric
transducers to
guarantee rated unit
production
24
action
activation
humidifi cation
ESC / Digital 29
interrupted
humidifi cation
ESC / Digital 29
interrupted
humidifi cation
automatic (after
interrupted
10 minute wait,
only per 10
see Chap. 5.8)
minutes
humidifi cation
ESC / Digital 29
interrupted
signal only
Reset hour
counter (See
Chap 5.6 or 6.8)
humidifi cation
AUTO
interrupted
humidifi cation
AUTO
interrupted
humidifi cation
AUTO
interrupted
humidifi cation
If this persists
interrupted
contact service
humidifi cation
If this persists
interrupted
contact service
humidifi cation
AUTO
interrupted
humidifi cation
AUTO
interrupted
yes
signal only
AUTO
no
signal only
AUTO
yes
signal only
Reset internal
piezoelectric
transducer
counter
by setting
parameter d6 to
zero (See chapter
5.8)
reset
Tab. 9.a