To access and set the following parameters, see chapters 6 and 12.
7.1 Basic parameters
Parameter
A0 Operating mode
0 = On/Off mode from auxiliary card probe input
1 = Proportional mode from auxiliary probe input
2 = Humidity probe mode from auxiliary card probe input
3 = Auto mode: if fi tted, humidity probe TH reading is used, otherwise On/Off mode from contact on main
board. Parameter A2 is not used
A1 Unit of measure 0 = Celsius ; 1= Fahrenheit
A2 Type of external sensor (optional card) (0 = On/Off ; 1 = 0-10V; 2 = 2-10V; 3 = 0-20 mA; 4 = 4-20 mA)
P0
Maximum production
P1
Proportional control hysteresis for mode A0=1
Pn Minimum production
SP
Humidity set point
SL
Humidity limit set point
bP
Proportional band for control with probe
bL
Proportional band for humidity limit
C0 Default display (Terminal)
0 = Probe reading/control signal;
1 = Hour counter
7.2 Advanced parameters
Parameter
A3
Probe minimum
A4
Probe maximum
A5
Probe off set
A6
Fan off delay time
A7
Fan speed
A8
Maximum evaporation time for reduced production alarm
A9
Minimum evaporation time for reduced production alarm
AA
Waiting time for retry
Ab
Percentage of A8 to carry out level test
AC
Maximum time to measure level when refi lling
Ad
Maximum time to measure high level
AE
Restart fan time in standby for integrated probe reading
AF
Piezoelectric transducer working life
b0
Operating options (see table for parameter b0)
b1
Time between two washing cycles
b2
Inactivity time for washing
b3
Washing time (fi ll + drain)
b4
Start delay time
b5
Operating hours for CL alarm
b6
Time to display new CL alarm after reset from keypad (without resetting hour counter)
b7
Transducer modulating control period
b8
Probe disconnected delay
b9
OFF delay from TAM
bA
Maximum fi ll time
bb
Water refi ll time in production
bC
Maximum drain time
bd
Drain opening time to completely empty tank
bE
Delay time after measuring low level for refi lling
bF
Drain activation delay in standby (if drain solenoid valve in standby = OPEN)
bH
Enable probe TH as humidity limit
bL
Proportional band for humidity limit
bP
Proportional band for control with probe
P1
Proportional control hysteresis for mode A0=1
P2
Low humidity alarm threshold
P3
High humidity alarm threshold
(1) To be able to modify the value on the terminal, the corresponding dipswitches must all be Off . To be able to use the value set by the dipswitches again, set one of the dipswitches to
On and power off . When powering on again, the controller will use the values set by the dipswitches.
(*) after 999 the display shows
(**) the default is 0 (zero), for humidifi ers without auxiliary card and without humidity/temperature probe.
Direct version for room applic. +0300062IE - rel. 1.3 - 15.07.2019
7.
CONFIGURATION PARAMETERS
to indicate the 1000s (the three digits are displayed with a dot at the top between the fi rst and second digit).
UOM
-
-
-
%
%
%
%rH
%rH
%rH
%rH
-
UOM
range
%rH
0...100
%rH
0...100
%rH
-99...100
min
0...15
%
40...100
min
0...200
min
0...A8
min
1...60
%
50...90
s
1...240
40 (UU02) - 60 (UU04) -
80 (UU06) - 100 (UU08)
s
1...60
min
0...120
h
0...9999
-
0...255
min/h
0...120
h
0...240
min
0...10
s
0...120
h
0...9999(*)
min
0...240
s
0...10
s
0...200
s
0...60
min
0...30
s
0...120
20 (UU02) - 28 (UU04) -
s
0...1500
75 (UU02) - 100 (UU04) -
150 (UU06) - 200 (UU08)
s
0...1500
60 (UU02) - 80 (UU04) -
120 (UU06) - 160 (UU08)
s
1...20
h
0...48
-
0...1
%rH
2...20
%rH
2...20
%
2...20
%rH
0...100
%rH
0...100
18
range
def
note
0...3
3
0...1
0
0...4
1
Pn...100 100
2...20
2
5...P0
10
20...80
50
only if terminal connected,
otherwise values set by dipswitch
0...80
70
2...20
10
2...20
10
0...1
0
def
note
0
100
0
5
50
30
1
10
70
10
10(**)
9999
with demineralised water
135
12
24
1
10
5000
60
1
30
2
6 (UU02) - 9 (UU04) -
12 (UU06) - 15 (UU08)
40 (UU06) - 52 (UU08)
10
1
0
if enabled, applies to
modes A0 = 0, 1, 2
10
10
2
20
80
Tab. 7.a
Tab. 7.f