ENG
ON
1
2
1.
Communication
OFF Serial 485 Carel/Modbus
ON tLAN
2-3 tLAN address (if 1 is ON)
OFF/OFF - -
OFF/ON address 1
ON/OFF address 2
ON/ON address 3
4
Serial 485 / tLAN baud rate
OFF
19200
ON
9600
3.3 Main board connections
Depending on the type of signal used, atomized water production can
be enabled and/or managed in diff erent ways (ON/OFF or modulating).
HUMIDISTAT OR REMOTE CONTACT (ON/OFF action)
Production is enabled by closing terminal M14.
M14 can be connected to a switch, a humidistat or a controller (voltage-
free contact, max 5 Vdc open, max 7 mA closed).
TH HUMIDITY PROBE (built-in on part numbers UU**R*AS01)
If the TH humidity probe is connected to the G terminal atomized water
production starts ifi :
•
The terminal M14 is closed;
•
The humidity value measured by the probe is below the setpoint
(preset at 50%rH and modifi ed via dipswitches 5-6).
485 SERIAL CONNECTION
Carel/Modbus protocol
RS 485
GND
Important: for RS485 connections in household (IEC EN 55014-1)
and residential (IEC EN 61000-6-3) environments, use shielded cable (with
shield connected to PE both on the terminal and controller ends),
maximum length specifi ed by the EIA RS485 protocol, equivalent to
European standard CCITT V11, using AWG26 twisted pair cable;
the input impedance of the 485 stage is 1/8 unit-load (96 kOhm). This
confi guration allows a maximum of 256 devices to be connected, with
cables in separate conduits from the power cable.
ALARM RELAY
The connections can be used to directly control a light or an auxiliary
relay coil or signal when reaching the humidity set point (see table of
parameter b0 values).
Direct version for room applic. +0300062IE - rel. 1.3 - 15.07.2019
3
4
5
6
7
8
Fig. 3.f
5-6 Humidity Setpoint
OFF/OFF 50 %rH
OFF/ON
30 %rH
ON/OFF
40 %rH
ON/ON
60 %rH
7
RESERVED
8
Production transducer managem.
OFF parallel
ON in series
G
G0
M 14
+ GND
Remote
ON/OFF
Fig. 3.g
M 11
-
+
Fig. 3.h
Note: in industrial environments (IEC EN61000-6-2) the signal cables
leaving the unit must not exceed 10 m (33 ft)
digital input (terminals M14.1...M14.2) and shielded cable for RS485
communication.
3.4 Auxiliary card connections
Tab. 3.b
See chap. "Confi guration parameters" for the description of parameters
A0, A1, A2.
The auxiliary card features the following connections
ON/OFF CONTROLLER (humidistat or remote switch)
•
jumper inputs M14.1 and M14.2 (enable) on the main board;
•
connect terminals M10.1 and M10.2 to a humidistat or a remote switch
(voltage-free contact);
•
set parameter A0=0 to enable On/Off operation.
EXTERNAL PROPORTIONAL CONTROLLER (modulating)
•
jumper inputs M14.1 and M14.2 (enable) on the main board;
•
connect terminals M10.1 and M10.2 (production request) to an
external controller;
•
set parameter A0=1 to enable modulating control and parameter A2
depending on the chosen signal (0 to 10 V, 2 to 10V, 0 to 20, 4 to 20 mA).
CONTROL WITH CAREL HUMIDITY PROBE
•
jumper inputs M14.1 and M14.2 (enable) on the main board;
•
connect the probe to terminals M10.1, M10.2. The power line M10.3
can be connected with cable of maximum length of 2 m (6,6 ft); for
greater lengths use an external power supply with the signal earth
electrically connected to the signal earth of the controller;
•
set parameter A0=2 to enable probe control and parameter A2
depending on the chosen signal (0 to 10 V, 2 to 10V, 0 to 20, 4 to 20 mA).
If non-CAREL probes are used, check:
•
voltage signal: 0 to 10 Vdc, 2 to 10 Vdc, terminal M10.1 (GND: M10.2);
•
current signal: 4 to 20, 0 to 20 mA, terminal M10.1 (GND: M10.2).
ENABLE PROBE TH AS HUMIDITY LIMIT
In control modes A0=0, A0=1, A0=2, the built-in humidity probe TH can
be used as a limit probe, setting parameter bH=1. The limit set point and
proportional band are set by parameters SL and bL.
Final checks
The following conditions represent correct electrical connection:
□ mains power to the humidifi er corresponds to the voltage shown on
the rating plate;
□ a mains disconnect switch has been installed so as to be able to
disconnect power to the humidifi er;
□ terminals M14.1, M14.2 are jumpered or connected to a contact to
enable operation;
□ if the humidifi er is controlled by an external controller (with auxiliary
card), the signal earth is electrically connected to the controller earth.
12
M9
M10
J8
5
1
2
3
4
NO
COMMON
Fig. 3.i
(1)
in length: remote on/off
M9
M10
J8
1
2
5
1
2
3
4
21 Vdc
NO
GND
Fig. 3.j
J17
J17