Controller operation

Miscellaneous

-
During summer or mid season, do not switch OFF the
main switch and the CDU breaker. Stop the CDU and
any heating/cooling operation, by setting code 0 to OFF.
Switching OFF the main switch or the CDU breaker, might
damage the CDU.
-
With code 33, it is possible to reduce the maximum
frequency of the compressor; if the maximum frequency
is reduced, the CDU will be less noisy but also less
powerful, therefore the auxiliary heaters, if available, will
be switched on more often.
-
When code 0 is set to OFF, the water pumps are switched
on for 10 minutes every day, to avoid the risk of pump
locking.
-
Inversion of heating to cooling operation or vice versa is
delayed for 3 minutes.

Installation

Unit Dimensions and Weights

See fi g. 22
See paragraph Features for data

Installation recommendations

Please refer to the Safety information manual.
-
This device is destined for installation in sheltered
buildings, if possible insulated.
It should not be installed in very humid rooms (for
example laundry rooms) or where it may be subjected to
water projections or spray.
-
The module is fi xed to the wall, make sure the support is
suffi ciently strong.
-
Fix the module using screws/wall plug fi xings adapted to
the wall structure and the module weight.
-
When possible, allow a space of minimum 70 cm below
and 30 cm on each side of the module for piping
connections and ease of maintenance.
16
80AW1- 80AWT - 80AW2
-
See paragraph Refrigerant connections for distances and
height diff erences between hydronic module and CDU.
-
In case of installation with fan coils, a minimum water
quantity of 4 liters / kW is required; install a buff er tank if
required.
-
The hydronic module has been fully tested by the
manufacturer; this could cause water residuals inside
the system. During installation phase, eventual water
residuals could come out from hydronic module water
connections.