Megger S1-5005 Guia Del Usuario página 27

Tabla de contenido

Publicidad

DD Test
Default test time of 30 minutes, followed by a 1 minute discharge
time.Terminating the test prematurely still allows the test results
to be calculated and displayed.
Timer
Digital Indicator
T3
Test Duration
Blank
T3 time
DD value
T3 time
R at T3 time
T3 time
at T3 +1 minute
T2 time
PI (T1 / T2)
T3 time
µF
Note: A capacitance value reading is only available if the test
has run for more than one minute, and provided the
reading was not over-range.
Voltage Indicator
Other
Final test voltage
DD cursor
Voltage at T3 time
flashes
Voltage at T3 time
Voltage at T3 time
PI cursor
Voltage at T2 time
flashes
Voltage at T3 time
SV Test
Test time set at 5 minutes only. Terminating the test prematurely
may cause some results to be displayed as - - -.
Timer
Digital Indicator
Test Duration
1,00 minute
R (at 1 minute)
R (at 2 minutes)
2,00 minute
3,00 minute
R (at 3 minutes)
4,00 minute
R (at 4 minutes)
5,00 minute
R (at 5 minutes)
Test Duration
Note: A capacitance value reading is only available if the test
has run for more than one minute, and provided the reading
was not over-range
Voltage Indicator
Blank
Final test voltage
Voltage at 1 minute
Voltage at 2 mins
Voltage at 3 mins
Voltage at 4 mins
Voltage at 5 mins
µF
Final test voltage
27