connect the utilities to the machine following the indications set out in this manual
and in the symbols on the panels of the machine itself;
the water circuit (condensate drain pipe, humidifier) contains harmful substances. Do
not drink from the hydraulic circuit and make sure the material contained in it does
not touch your skin, eyes or clothing.
in order to avoid an environmental risk, make sure that any leaking fluid is collected
in suitable devices in accordance with local regulations
if a part needs to be dismantled, make sure that it is correctly re-assembled before
starting the unit;
when the rules in force require the installation of fire-fighting systems near the
machine, check that these are suitable for extinguishing fires on electrical equipment
and on the lubricating oil of the compressor and the refrigerant, as specified on the
safety data sheets of these fluids (for example, a CO
keep all lubricants in suitably marked containers
do not store inflammable liquids near the unit
solder or braze only empty pipes after removing all traces of lubricant oil; do not use
flames or other heat sources in the vicinity of pipes containing refrigerant fluid
do not use naked flames near the machine;
the machinery must be installed in structures protected against atmospheric
discharge according to the applicable laws and technical standards
do not bend or hit pipes containing pressurised fluids
it is not permitted to walk or rest other objects on the machines
the user is responsible for overall evaluation of the risk of fire in the place of
installation (for example, calculation of the fire load)
during transport, always secure the unit to the bed of the vehicle to prevent it from
moving about and overturning
the machine must be transported according to the regulations in force taking into
account the characteristics of the fluids in the machine and the description of these
on the safety data sheet
inappropriate transport can cause damage to the machine and even leaking of the
refrigerant fluid. Before the first start up, check that the cooling circuit is pressurised;
the accidental discharge of refrigerant in a closed area can cause a lack of oxygen
and, therefore, the risk of asphyxiation: install the machine in a well-ventilated area
according to the EN 378-3 standard and the local regulations in force, and refrigerant
detectors whenever required;
unless arranged otherwise with the Manufacturer, the machine be installed in
environments where there is no risk of explosion (SAFE AREA)
1.1.6

LIST OF MACHINE INTERNAL SYMBOLS

Equipment
Danger of burns
under voltage
Earth connection
1.1.7

ACOUSTIC DATA

Standard machine acoustic data in full load operating conditions.
In a closed environment, the noise of a sound source reaches the individual in two different
ways:
Directly;
Reflected by the surrounding walls, floor, ceiling and furniture.
With the same sound source, the noise produced in a closed environment is stronger than
outside. This is because the noise directly produced by the source is amplified as it bounces
around the objects. The shape of the room also affects noise levels.
MODEL
MODEL
SOUND LEVEL ISO 3744 (1)
SOUND LEVEL ISO 3744 (1)
dB(A
Sound pressure
Sound pressure
)
Sound power
dB(A
Sound power
)
1.
Sound pressure level at 1 metre, free field - ISO EN 3744
1.1.8

PROCEDURE FOR REQUESTING SUPPORT

For support, please contact one of the authorised centres (Italy) or our branches/distributors
(outside Italy). When requesting technical support concerning the machine, cite the data on
the identification plate and the serial number, also describe the conditions of access and the
area around the machine.
In your request, indicate the approximate hours of use and the fault detected. In case of
alarm, indicate the alarm message number.
UM_MULTIDENSITY_00_Z_09_20_ML
extinguisher)
2
Internal moving
components
Check the drain
009
015
025
63.5
64.5
70.5
79.0
80.0
86.0
1.2

MACHINE IDENTIFICATION

1.2.1

NOMENCLATURE

The alphanumerical code of the model of the machine, which is given on the identification
plate, represents precise technical specifications which are indicated in the figure.
INTERNAL UNIT
m-MROW-G02-009 INDOOR UNIT:
m-M
Series
ROW
Unit type
G02
Refrigerant
009
Unit size
m-MOCU-G02-050 OUTDOOR UNIT:
m-M
Series
OCU
Unit type
OCU = outdoor condensing unit
G02
Refrigerant
050
Unit size
1.2.2

IDENTIFICATION PLATE

The type of machine is shown on the label on the machine, normally found in the electrical
panel.
The label provides the reference data and all the essential information required to ensure
safe operation, as shown in the example below.
IDENTIFICATION PLATE
18
English
m = Multidensity system
M = Mitsubishi brand
ROW = in-row version
RAC = enclosure version
G02 = R410A
m = Multidensity system
M = Mitsubishi brand
G02 = R410A
m–MROW-G02-025
BL92xxxxx
01234567
2020
193 kg
R410A
2088
N.A.
230Vac / 1 /50Hz
0.85
3.9
8.8
8.8

Indoor Unit

4.15 MPa
ORIGINAL INSTRUCTIONS