6.3.4 Probe menu

Touch
to enter menu
Touch
to go ahead
real-time probe values are displayed:
iB0
: Dew point temperature
iB2
: Evaporator temperature
iB8
: Discharge compressor temperature
iB5
: Suction compressor temperature
iB3
: Ambient temperature
iP1
: High pressure (condenser)
English

6.3.5 Digital input menu

Touch
to enter menu
Local ON/OF: green when remote start contact is closed, otherwise it
is gray.
Condensate level: green when there is condensation to drain, otherwise
it is gray.
Monitoring phase: green when phase sequence is correct, otherwise
it is gray:
Compressor protection: green when compressor protection is in the
normal operating position, otherwise it is gray.
High Pressure switch: green when pressure switch protection is in the
normal operating position, otherwise it is gray.
Low Pressure switch: green when pressure switch protection is in the
normal operating position, otherwise it is gray.
PSE 120-350

6.3.6 Digital output menu

Touch
to enter on menu
General alarm:green when general alarm contact is closed, otherwise
it is gray.
Compressor: green when compressor start contact is closed, otherwise
it is gray.
Condensate drain: green when condensate drain contact is closed,
otherwise it is gray.
Plan Status: green when dryer on contact is closed, otherwise it is gray.
Hot gas bypass valve: green when bypass valve contact is closed
(valve open), otherwise it is gray.
9/12