Wiring Your Controller - Allen-Bradley SLC 500 1747-L20 Instrucciones De Instalación

Controladores tipo hardware compacto
Tabla de contenido

Publicidad

All manuals and user guides at all-guides.com

Wiring Your Controller

See page 104 to locate the wiring diagram for your controller.
ATTENTION
Before you install and wire I/O devices, disconnect power from
the controller and any other source to the I/O devices.
Use acceptable wire gauge - The I/O wiring terminals are designed to accept #14
Use acceptable wire gauge
Use acceptable wire gauge
Use acceptable wire gauge
or smaller AWG stranded wires, and two wires per terminal (maximum). Maximum
torque 0.9 N-m (8 in-lb.).
Label wires - Label wiring to I/O devices, power sources, and ground. Use tape,
Label wires
Label wires
Label wires
shrink-tubing, or other dependable means for labeling purposes. In addition to
labeling, use colored insulation to identify wiring based on signal characteristics. For
example, you may use blue for dc I/O wiring and red for ac I/O wiring.
Bundle wires - Bundle wiring for each similar I/O device together. If you use ducts,
Bundle wires
Bundle wires
Bundle wires
allow at least 5 cm (2 in.) between the ducts and the controller so there is sufficient
room to wire the devices.
Identify terminals
dentify terminals - Terminal cover plates have a write-on area for each terminal.
dentify terminals
dentify terminals
Use this area to identify your I/O devices. Label the Removable Terminal Block
(RTB) with appropriate slot, rack (chassis) and module identification if you have not
already.
Power
Power - The fixed controllers are equipped with an auto-ranging power supply. This
Power
Power
means that you can connect either 120V ac or 240V ac to the controller, and the
controller power supply will automatically configure itself to operate with the
applied voltage.
Calculate the maximum possible current in each power and
ATTENTION
common wire. Observe all local electrical codes dictating the
maximum current allowable for each wire size. Current above the
maximum ratings may cause wiring to overheat, which can cause
damage.
SLC 500™ Fixed Hardware Style Controllers
Publication 1747-IN008B-MU-P
11

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Slc 500 1747-l30Slc 500 1747-l40

Tabla de contenido