SLC 500™ Fixed Hardware Style Controllers

Output Specifications

Outputs
Triac
Transistor Sink &
Source
(2)
Relay
(1) Repeatability is once every 1 second at +30°C. Repeatability is once every 2 seconds at +60°C.
(2) Surge suppression across the output device is recommended to protect relay contacts.
(3) Refer to the wiring diagrams, beginning on page 104, for output groupings on the fixed I/O chassis.
Publication 1747-IN008B-MU-P
Specifications
Output Voltage
Continuous Current (per output)
Minimum Load Current
Turn-On Time
Turn-Off Time
Maximum Off-State Leakage
Current
Maximum On-State Voltage Drop
Maximum Surge Current
Output Voltage
Continuous Current (per output)
Minimum Load Current
Turn-On Time
Turn-Off Time
Maximum Off-State Leakage
Current
Maximum On-State Voltage Drop
Maximum Surge Current
Output Voltage Range
Continuous Current (per output)
Continuous Current (per group)
Maximum Load (per chassis)
Turn-On Time
Turn-Off Time
Maximum Off-State Leakage
Current
Minimum Load Current at 5V dc
85-265V ac
0.5A at +30°C
0.25A at +60°C (maximum)
10mA
0.1 ms (maximum)
10 ms (maximum)
2mA
1.5V at 0.5A
(1)
10A for 25 ms
10-50V dc
0.5A at +30°C
0.25A at +60°C (maximum)
1mA
0.1 ms (maximum)
1 ms (maximum)
1mA
1.5V at 0.5A
3.0A for 25 ms
5-265V ac, 5-125V dc
See Relay Contact Rating table on
page 18
(3)
8A (maximum)
1440 VA
10 ms (maximum)
10 ms (maximum)
0mA
10mA
(1)