Specifications - Allen-Bradley SLC 500 1747-L20 Instrucciones De Instalación

Controladores tipo hardware compacto
Tabla de contenido

Publicidad

All manuals and user guides at all-guides.com
16
SLC 500™ Fixed Hardware Style Controllers

Specifications

Description
Memory Type
Memory Backup Options
Program Memory
Battery Life
Capacitor Memory Back-Up Time
(2)
Typical Scan Time
Bit Execution (XIC)
Program Scan Hold-up Time after Loss of Power 20 ms to 700 ms (dependent on loading)
Power Supply Operating Voltage
Power Supply Fuse Protection
Power Supply Inrush Rating
Maximum Power Requirement
24V dc User Power Output Current
24V dc User Power Output Voltage
Wire Size
I/O Electrical-Optical Isolation
1747-AIC Link Coupler Electrical-Optical
Isolation
Noise Immunity
Ambient Temperature Rating
Humidity
Vibration
Agency Certification
(1) For further information, refer to the Fixed Hardware Style Installation and Operation Manual , Publication
1747-6.21.
(2) The scan times are typical for a 1K ladder logic program consisting of simple ladder logic and
communication servicing. Actual scan times depend on your program size, instructions used, and the
DH-485 communication.
(3) This specification does not include input and output values. ( S ee page 17.)
(4) This applies only to fixed controllers that have ac line power and dc input circuits.
Publication 1747-IN008B-MU-P
Specification
Capacitor-backed RAM memory. Battery back-up
optional.
EEPROM or UVPROM
1K Instruction Capacity
5 years
(1)
30 days at 25°C (77°F)
5 days at 60°C (140°F)
8 ms/1K
4 µs
ac units: 85-265V ac 47-63 Hz
dc units: 21.6-26.4V dc (24V dc ± 10%)
ac units: 120/240V ac 1.25A
dc units: 24V dc 1.6A
30A (maximum)
(3)
50 VA
(4)
200 mA
(4)
20.4 - 27.6V dc (24V dc ± 15%)
#14 AWG (maximum), 2 wires per terminal
1500V ac at 1 min.
1500V dc
NEMA Standard ICS 2-230
Operating: 0°C to +60°C (+32°F to +140°F)
Storage: -40°C to +85°C (-40°F to +185°F)
5 to 95% without condensation
Displacement: 0.015 inch, peak-to-peak at 5-57
Hz
Acceleration: 2.5 Gs at 57-2000 Hz
Duration: 1 hr. per axis (x, y, z)
UL listed/CSA approved