BTL6-A500/B50 _ -M _ _ _ _ -E2/E28-KA _ _/LA _ _-ZA0 _
Micropulse AT transducer in round profile housing
Shielding and cable routing
Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect transducer and controller using a shielded
cable.
Shielding: Braided copper shield with minimum 85%.
Connector version: Shield is internally connected to
connector housing.
Cable version: On the transducer side, the cable
shielding is connected to the housing.
Ground the cable shielding on the controller side
(connect with the protective earth conductor).
Magnetic fields
The position measuring system is a magnetostrictive
system. It is important to maintain adequate distance
between the transducer cylinder and strong, external
magnetic fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Bending radius
Fixed routing
Cable length
The maximum cable length is 20 m 1).
1) Prerequisite: Construction, shielding and routing preclude the effect of
any external noise fields.
www.balluff.com
3 x cable Ø
Startup
DANGER
Uncontrolled system movement
When starting up, if the position measuring system is
part of a closed loop system whose parameters have not
yet been set, the system may perform uncontrolled
movements. This could result in personal injury and
equipment damage.
Persons must keep away from the system's
f
hazardous zones.
Startup must be performed only by trained technical
f
personnel.
f
Observe the safety instructions of the equipment or
system manufacturer.
1.
Check connections for tightness and correct polarity.
Replace damaged connections.
2.
Turn on the system.
3.
Check measured values and adjustable parameters
regularly (especially after replacing the transducer or
after repair by the manufacturer).
Operating notes
Check the function of the transducer and all associated
components on a regular basis.
Take the position measuring system out of operation
whenever there is a malfunction.
Secure the system against unauthorized use.
EMC characteristics can only be ensured if the
BTL6-A/B...-ZA0_ is completely installed in a
grounded metal housing.
english
3