EXCLUSIVE X
Vent cycle
b
Each time that the boiler is powered, an automatic vent cycle is carried out lasting
6 min. When the vent cycle is in progress, all heat requests are inhibited except for
domestic hot water ones when the boiler is not set to OFF, and a scrolling message
X6
at the foot of the page appears on the main page of the REC10CH.
X3 X7
1
b
The vent cycle can be interrupted beforehand by removing the cap from the
instrument panel and pressing the combustion analysis button SW1 or else from the
TECHNICAL menu of the REC10CH in the following way:
- select TECHNICAL
AIR PURGING CYCLE
TECHNICAL
WEATHER COMPENSATION
RANGE RATED
CALIBRATION
COMBUSTION ANALYSIS
AIR PURGING CYCLE
INSTALLER
The REC10CH will briefly display a wait message after which you will automatically be taken
to the main screen. The vent cycle can also be interrupted, if the boiler is not set to OFF, by
a domestic hot water request.
1
4
1 3
1
5
1
FRI
09/04/2021
MENU
X13
X8
X21
X2
SUMMER
(only if a water tank is connected): select STATE
HOT WATER ONLY (SUMMER) to activate the traditional function of only domestic hot
water. The REC10 normally displays the temperature of the domestic hot water stocked in
the water tank (only in case of water tank with probe).
In case of water tank with thermostat or domestic hot water request in progress, the delivery
boiler temperature is displayed.
WINTER
/
: select STATE
WATER (WINTER) to activate heating and domestic hot water functions. The REC10CH
normally displays the domestic hot water temperature unless there is a heating request in
progress, in which case the boiler's outlet temperature is displayed.
4.4
Adjusting the heating water temperature without an outdoor
temperature sensor connected
The HEATING setpoint can be set by selecting SET in the REC10CH main screen and choosing
[40°C ÷ 80.5°C] for high temperature systems and [20°C ÷ 45°C] for low temperature
16
combustion analysis
SW1
button SW1
STOP FUNCTION
5
X14
AIR PURGING CYCLE
1
FUNCTION ENABLED
X12
FUNCTION DISABLED
STOP FUNCTION
INSTALLER
4
PLANT
12:17
bar
STATE
1.3
30
°C
.3
INFO
SET
HOT WATER TEMPERATURE
BOILER
OFF
HOT WATER ONLY
HEATING AND HOT WATER
BOILER
BOILER
OFF
HOT WATER ONLY
HEATING AND HOT WATER
SET
SET
HEATING
HEATING
DHW
HOT WATER
4.5
Adjusting the heating water temperature with an outdoor
temperature sensor connected
The outlet temperature value is automatically chosen by the system, which rapidly adjusts
the room temperature according to the variations in the external temperature.To modify the
temperature value, increasing or decreasing it with respect to that automatically calculated
by the electronic board, it is possible to act on the HEATING setpoint by selecting SET in
the REC10CH main screen and choosing the desired comfort level within the range (-5 ÷
+5) (see "4.2.5 Setting the thermoregulation"). Note: when there is an outdoor temperature
sensor connected it is still possible to have the boiler operate at a fixed point setting the
values of MIN SP HEAT and MAX SP HEAT at the desired HEATING setpoint.
4.6
Adjusting the domestic hot water temperature
CASE A: only heating with no external water tank connected - adjustment not applicable.
CASE B: only heating with an external water tank managed by a thermostat - adjustment
not applicable.
CASE C: only heating with an external water tank managed by a probe.
To set the domestic hot water temperature (bath, shower, kitchen, etc.): SET
choose the desired value between the range [37,5°C ÷ 60°C].
4.7
Adding devices
- Select TECHNICAL
Then complete the configuration of the water tank referring to the specific section ("4.18
Water tank configuration").
b
After adding the water tank, DHW is displayed on the "Programme" page. This
function allows the domestic hot water programming timing to be carried out
4.8
Boiler start-up
If there is a room thermostat or a programming timer, or the REC10CH MASTER is set as
an ambient regulator, it is necessary that these are on and that they have been adjusted
to a temperature higher than the ambient temperature so that the boiler switches on. The
boiler will be in standby until the burner switches on following a heat request. The display
shows
BOILER
The boiler will be in function until the selected temperature is reached, afterwards it will
be in "standby" again keeping the outlet temperature displayed. If faults arise in ignition or
operations, the boiler performs a "SAFETY STOP": the triangle signalling faults will flash on
the REC10CH. To identify the fault codes and to reset the appliance, see the section "4.14
Lights and faults".
HEATING AND HOT
4.9
Reset function
In the event of a lockout, it is possible to try and reset normal operations by pressing "OK" on
the REC10CH when the fault message is displayed to reset the alarm in progress.
b
If the release attempts do not restart the boiler, contact your local Technical
Assistance Centre.
4.10
Screed heater function
For a low temperature system the boiler has a "screed heater" function that can be activated
in the following way:
systems.
- set the boiler to OFF
- select SCREED HEATING (Note: SCREED HEATING is not available if the boiler is not OFF)
- select FUNCTION ACTIVE or FUNCTION NOT ACTIVE and confirm to enable /disable
the function.
SET
SET
HEATING
HEATING
DHW
HOT WATER
ADD WATER TANK
to indicate the presence of a flame.
FRI
PLANT
18/05/2013
bar
MENU
1.3
42
°C
INFO
HOT WATER TEMPERATURE
E010
FLAME LOCKOUT
OK TO RESET
TECHNICAL
RANGE RATED
CALIBRATION
COMBUSTION ANALYSIS
EXHAUST PROBE RESET
SCREED HEATING
INSTALLER
DHW to
.
12:17
STATE
SET