Bosch MS 200 Manual De Instrucciones página 34

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 38
Commissioning
Menu item
Adjustment range: Function description
Collector cooling
Yes: Collector array 1 is actively cooled via the connected
function
emergency cooler when 100 °C (= Max. collector temp. –
20 °C) is exceeded.
No: Collector cooling function switched off.
Table 10 Solar circuit
Cylinder
WARNING:
Risk of scalding!
▶ If DHW temperatures above 60 °C are set or thermal disinfection is
switched on, a mixer must be installed.
Menu item
Adjustment range: Function description
Max. temp. cyl. 1
Off: 1st cylinder is not heated.
20 ... 60 ... 90 °C: If the temperature set here is exceeded
in cylinder 1, the solar pump is off.
Max. temp. cyl. 2
Off: 2nd cylinder is not heated.
20 ... 60 ... 90 °C: If the temperature set here is exceeded
in cylinder 2, the solar pump is off or the valve is closed
(subject to the selected function).
Max. pool temp.
Off: The swimming pool is not heated.
20 ... 25 ... 90 °C: If the temperature set here is exceeded
in the swimming pool, the solar pump is off or the valve is
closed (subject to the selected function).
Max. temp. cyl. 3
Off: 3rd cylinder is not heated.
20 ... 60 ... 90 °C: If the temperature set here is exceeded
in cylinder 3, the solar pump is off, the pool pump is off, or
the valve is closed (subject to the selected function).
Priority cylinder
Cylinder 1
Cylinder 2 (Pool)
Cylinder 3 (Pool)
The cylinder set up here is the high priority cylinder;
 function Cylinder 2 with valve (B), Cylinder 2 with
pump (C) and Cylinder 3 with valve (N). The cylinders are
heated in the following order:
Priority cylinder 1: 1 – 2 or 1 – 2 – 3
Priority cylinder 2: 2 – 1 or 2 – 1 – 3
Priority cylinder 3: 3 – 1 – 2
Test interval
15 ... 30 ... 120 min: If the low priority cylinder is
priority cyl.
currently being heated, the solar pumps are switched off
at the regular intervals specified here.
Test duration
5 ... 10 ... 30 min: While the solar pumps are switched off
priority cyl.
( Test interval priority cyl.), the temperature in the
collector increases and the required temperature
differential for heating the high priority cylinder may be
reached during this period.
Elapsed time
10 ... 120 ... 600 s: The elapsed time set here determines
valve cyl. 2
how long it takes the 3-way valve to switch from cylinder 1
to cylinder 2, or vice versa.
Switch-on diff.
6 ... 20 K: If the differential set here between the cylinder
heat ex.
temperature and the temperature at the heat exchanger is
exceeded and all conditions for switching on have been
met, the cylinder primary pump is on.
Switch-off diff.
3 ... 17 K: If the differential between the cylinder
heat ex.
temperature and the temperature at the heat exchanger falls
below the value set here, the cylinder primary pump is off.
Frost prot. temp.
3 ... 5 ... 20 °C: If the temperature at the external heat
heat ex.
exchanger falls below the temperature set here, the
cylinder primary pump is on. This protects the heat
exchanger from damage from freezing.
Table 11 Cylinder
34
All manuals and user guides at all-guides.com
Central heating backup(
Menu item
Start diff. ctrl. heat
back.
End diff. ctrl. heat.
back.
Max. mixer temp.
CH
Mixer elapsed time
CH
Table 12 Central heating backup
Solar yield/optimisation
The gross collector area, collector version and climate zone number
must be set correctly in order to achieve maximum energy savings and to
display the correct value for the solar yield.
The value of the solar yield, is a calculated yield estimate. Measured values
are displayed with the function heat meter (L) (Accessories WMZ).
Menu item
Gross collector
area 1
Type collector
array 1
Gross collector
area 2
Type collector
array 2
Climate zone
Min. DHW temp.
)
Adjustment range: Function description
6 ... 20 K: If the differential set here between the cylinder
temperature and heating return is exceeded and all
conditions for switching on have been met, the cylinder is
integrated in the heating return for central heating backup
via the 3-way valve.
3 ... 17 K: If the differential between the cylinder
temperature and the heating return falls below the value
set here, the cylinder is bypassed via the 3-way valve for
central heating backup.
20 ... 60 ... 90 °C: The temperature set here is the
maximum temperature permitted in the heating return
when achieved via central heating backup.
10 ... 120 ... 600 s: The elapsed time set here determines
how long it takes the 3-way valve or the 3-way mixer from
"cylinder to be fully integrated in heating return" on to
"bypass for the cylinder", or vice versa.
Adjustment range: Function description
2
0 ... 500 m
: This function allows you to set the area
installed in collector array 1. The solar yield is only
2
displayed if an area > 0 m
is set.
Flt-pl. col: Use of flat plate collectors in collector array 1
Vacuum tube collector: Use of vacuum tube collectors in
collector array 1
2
0 ... 500 m
: This function allows you to set the area
installed in collector array 2. The solar yield is displayed if
2
an area > 0 m
is set.
Flt-pl. col: Use of flat plate collectors in collector array 2
Vacuum tube collector: Use of vacuum tube collectors in
collector array 2:
1 ... 90 ... 255: Climate zone of the installation location
according to the map ( Fig. 43 at the end of the
document).
▶ Search for the location of the system on the climate
zones map and set the climate zone number.
Off: DHW reheating via the heat appliance irrespective of
the minimum DHW temperature
15 ... 45 ... 70 °C: The control system determines whether
solar yield is available and whether the stored amount of
heat is sufficient to supply DHW. The control system then
reduces the set DHW temperature to be produced by the
heat appliance in accordance with these two values. If
there is sufficient solar yield, there is therefore no need to
reheat the DHW with the heat appliance. If the
temperature set here is not reached, the DHW is reheated
by the heat appliance.
MS 200 – 6720879925 (2017/11)

Publicidad

Tabla de contenido
loading

Tabla de contenido