Observe the current type and voltage on the rating plate.
Connect to 230 V low-voltage networks. When connecting to IT networks (Isolé Terre electrical system), al-
ways make sure that the voltage between the live wires (L1-L2, L2-L3, L3-L1 ➜ Fig. 3) does not exceed
230 V.
In case of error (earth fault), the voltage between the live wire and PE must not exceed 230 V.
During external connection of the pump, deactivate a pulse of the voltage (for example phase angle con-
trol).
Switching the pump via triacs/solid-state relays must be examined on a case-by-case basis.
During deactivation with on-site power relay: Rated current ≥ 10 A, rated voltage 250 V AC
Observe the switching frequency:
– Switch-on/off procedures via mains voltage ≤ 100/24 h
– ≤ 20/h for a switching frequency of 1 min. between switching on/off via mains voltage
If a residual-current device (RCD) is used, it is recommended to use an RCD type A (pulse current sensitive).
Check that the rules for the coordination of electrical equipment in the electrical installation are observed
and, if necessary, adjust the RCD accordingly.
Observe leakage current I
The electrical connection must be made via a fixed connecting cable equipped with a connector device or an
all-pole switch with a contact opening width of at least 3 mm (VDE 0700/Part 1).
To protect against leakage and for strain relief to the threaded cable gland, use a connection pipe with suf-
ficient outer diameter (see chapter "Connecting").
Use a heat-resistant connecting cable for fluid temperatures exceeding 90 °C.
Lay the connecting cable in such a way that it does not make contact with the pipes or the pump.
7.2

Connection options

Fig. 3: Connection options
The pump can be connected to power supplies with the following voltage ratings:
1~ 230 V
3~ 400 V with neutral conductor
3~ 400 V without neutral conductor (upstream mains transformer)
3~ 230 V
7.3

Twin-head pumps

Only operate as main and standby pump with automatic fault-actuated switchover:
Installation and operating instructions • Wilo-Yonos MAXO/-D/-Z • Ed.01/2022-08
≤ 3.5 mA for each pump.
eff
en