Put into operation

8.1

Venting

1.
Charge the system appropriately and ventilate.
▶ The pump is self-ventilating.
8.2

Flush

CAUTION
Damage to property!
While using fluids with admixtures, property damage can occur due to the accumulation of
chemicals.
• Flush system before commissioning.
• Flush out the pump before pouring in, refilling or replacing fluid.
• Remove the pump before change in pressure flushes.
• Do not perform any chemical flushes.
8.3

Select operating mode

Fig. 4: Select operating mode
Control mode
Variable differential pressure
Δp-v
Constant speed
n = const.
Constant differential pressure
Δp-c
Installation and operating instructions • Wilo-Yonos MAXO/-D/-Z • Ed.01/2022-08
Description
The control changes the differential pressure setpoint to be maintained by
the pump linearly between reduced differential pressure H and H
The controlled differential pressure H decreases or increases with the flow
rate.
The speed of the pump is kept at a set constant speed.
The control keeps the differential pressure created by the pump constant
above the permitted flow rate at the selected differential pressure setpoint
H
up to the maximum characteristic curve.
setpoint
en
.
target
57