16.1 Electrical data
The following electrical data refer to the basic unit without accessories.
In all other cases, refer to the electrical data in the wiring diagram attached to the unit.
The supply voltage must not vary more than ± 10% of the nominal value and the unbalance between phases
must be less than 1% according to EN 60204.
Please contact our technical department in case these tolerances are not respected.
MODEL
Power supply
Control circuit
Electrical data may change without notice. Therefore, ALWAYS refer to the wiring diagram supplied with the
unit.
16.2 Power supply connection
The electrical panel is located inside the unit and it is accessible through the inspection door interlocked by mainswitch on the
front of the unit (inspection side). To connect the power supply, use the cable gland on the front panel and connect the power
cable inside the electrical cabinet to the disconnecting switch with fuses.
045
400/3/50
V/Ph/Hz
060
080
400/3/50
400/3/50
12 VDC / 24 VAC
EN
100
130
400/3/50
400/3/50
38