Installation
6.3.2.2
Control unit connection
The connections are located on a manifold in the housing (pre-assembled in the
factory).
1
"PIS" pressure sensor
2
"SV" safety valve
3
Compressed air connection
4
"PV" solenoid valve
5
Weight measuring cell "LIS"
Install the weight measuring cell, 6.3.3 "Installation of the weight measuring
cell", 20.
6.3.3
Installation of the weight measuring cell
ATTENTION
Damage to the pressure load cell due to unprofessional installation
Incorrect installation may result in damage to the "LIS" level sensor,
malfunctioning and incorrect measurements from the pressure load cell.
•
Comply with the instructions regarding the installation of the pressure
load cell.
Install the weight measuring cell for the "LIS" filling level measurement, when
the primary vessel is located in the final position, 6.3.1 "Locating the vessel",
19. Comply with the following instructions:
•
Remove the transport safety device at the mounting foot of the primary
vessel.
•
Replace the transport safety device with the weight measuring cell.
•
Avoid shock-type loading of the load measuring cell by, for example,
subsequent alignment of the vessel.
•
Install the M12 plug on the weight measuring cell. (hand-tight)
Standard values for filling level measurements:
Primary vessel
80 l
6.4
Make-up and degassing variants
6.4.1
Function
The filling level in the primary vessel is measured by the "LIS" weight measuring
cell and evaluated in the controller. When the water level falls below the set
value, the external make-up is activated.
20 — English
Measuring range
0 – 4 bar
Reflexomat XS — 02.16.2022 - Rev. A
6.4.1.1
Make-up without pump
Reflexomat XS with Fillvalve.
1
Reflexomat XS
2
Fillvalve
3
Reflex Fillset
Preferably, you should use the Reflex Fillset with integrated system separator
when using potable water for make-up, 4.6 "Optional equipment and
accessories", 18.
6.4.1.2
Make-up with pump
The make-up systems, Reflex Fillcontrol Auto or Reflex Fillcontrol Auto Compact
can be used for make-up with a pump.
Water make-up with Fillcontrol Auto is suitable for make-up at high system
pressures of up to 8.5 bar.
6.4.1.3
Make-up with softening and degassing
Reflexomat XS and Reflex Servitec S.
1
Reflexomat XS
2
Reflex Servitec S
3
Reflex Fillsoft
4
Reflex Fillset Impulse
The Reflex Servitec S degassing and make-up unit degasses the water from the
system circuit and the make-up water. The automatic make-up for the system
circuit is controlled by the pressure maintenance system. Reflex Fillsoft
additionally softens or demineralises the make-up water.
•
Reflex Servitec degassing and make-up unit, 4.6 "Optional equipment
and accessories", 18.
Reflex Fillsoft softening system and Reflex Fillset Impulse, 4.6 "Optional
•
equipment and accessories", 18.
Note!
In a setup with a Reflex Fillsoft water treatment system, always install
the Reflex Fillset Impulse.
•
The controller evaluates the make-up quantity and signals the
necessary replacement of the softening or demineralisation
cartridge.
WC
Make-up line
LIS
Weight measuring cell
EC
Expansion line
WC Make-up line
LIS
Filling level measurement
EC
Expansion line