3.4.2.5.1 MODBUS
Slave address
1-247
Maximum Modbus
256 bytes
packet size
Supported baud rates
1200, 2400, 4800,
9600, 19200, 38400
Stop bits
1 or 2
Parity bit
Even/odd/none
3.4.2.5.2 BACNET
Device MAC address
1-127
Maximum ADPU size
92 bytes
Supported baud rates
9600, 19200, 38400
Modbus RTU over RS-485
See section Errore. L'origine riferimento non è s
tata trovata. Errore. L'origine riferimento non è
stata trovata..
[default=245]
Including address (1) and CRC (2) bytes.
Settable over Modbus register.
Settable over Web interface (tab "Network").
[default=19200]
1 stop bit minimum, up to 2 when parity not
enabled
[default=1]
[default=Even]
BACnet MS/TP over RS-485
Settable over Web interface (tab "Network")
[default=1]
Settable over Web interface (tab "Network")
[default=38400]