CAUTION
Cold/hot pipelines and/or ball valve.
Risk of injury due to thermal influences!
Insulate the ball valve.
Attach warning signs.
Medium escaping at high speed and high/low temperature.
Risk of injury!
Wear the prescribed protective equipment
Improper disassembly of the actuator.
Personal injury and property damage
Disassembling a pressurised actuator leads to uncontrolled pressure relief!
Before dismantling the actuator, close the pressure supply
Release the pressure from the cylinder.
NOTICE
Impermissible stress due to operating conditions and extensions / added structures.
Leakage or rupture of the valve body!
Provide suitable support.
Additional loads such as traffic, wind or earthquakes are not explicitly considered as standard
and require a separate design.
Condensation in air conditioning, cooling and refrigeration plants.
Icing!
Blocking of the actuation mechanism!
Damage due to corrosion!
Insulate the ball valve diffusion-tight
Incorrect installation.
Damage to the ball valve!
Remove caps before installation.
Clean the sealing surfaces.
Protect the housing from impacts.
Painting of ball valve and pipelines.
Functional impairment of the ball valve / loss of information!
Protect stem, plastic parts and type plate against the application of paint.
Impermissible stress.
Damage to the control mechanism!
Do not use the ball valve as a foothold.
Exceeding the maximum permissible operating conditions.
Damage to the ball valve!
The maximum permissible working pressure must not be exceeded, and the minimum and
maximum allowable working temperatures must be observed.
Lay the welding/brazing bead in several sections so that the heat build-up in the middle of the
enclosure does not exceed the maximum permissible operating temperature.
Particles and other contaminants in the conveyed medium.
Damage to the ball valve / internal leak!
Remove particles/contaminants from the conveyed medium.
It is recommended to install strainers / dirt filters in the pipework system.
Incorrect earthing during welding work in the pipeline.
Damage to the ball valve (burned spots)!
Remove bonnet during welding.
Do not use any parts of the valve for earthing during electric welding work.
Operating instructions
herose.com
19

Publicidad

Tabla de contenido
loading

Tabla de contenido