S
et thermoStat to adjuSt indoor air cfm trim
User can change the airflow trim at high, intermediate and
low compressor speed.
Select:
Cool Airflow trim High: -15% ~ +15%
Cool Airflow trim Intermediate: -15% ~ Full*
Cool Airflow trim Low: -15% ~ Full*
Heat Airflow trim High: -15% ~ +15%
Heat Airflow trim Intermediate: -15% ~ +15%
Heat Airflow trim Low: -15% ~ +15%
Under each trim setting, the airflow can be increased or
decreased by a certain percentage.
* The Inverter system uses lower compressor speed and lower
indoor unit CFM to optimize system performance.
To obtain 100% CFM for home circulation, use full Trim setting
instead of Int/Low speed.
This is recommended for applications with unusual cold return
temperatures such as basements.
NOTE: Trim settings of the following combinations are restricted.
Outdoor
ASXS6*361*A*/ASZS6*361*A*
Unit
A*VC960403B/0603B
A*VM970603B
Indoor
A*VC800603B/0803B
Unit
MBVC1200
A*VS960805CU
Outdoor
ASXS6*601*A*/ASZS6*601*A*
Unit
A*VC960804C
Indoor
A*VM970804C
Unit
A*VC800804C
Depending on the connected indoor unit, there are restrictions on
the positive side Trim setting.
If you want to change the Cool Airflow Trim to positive side, be
sure to confirm the Airflow Trim restrictions in the latest indoor unit
installation manual.
To see any restriction of added new combination, the latest
manual can be obtained from the website "PartnerLink
(InfoFinderPlus/Literature)".
[PartnerLink URL]
https://partnerlinkmarketing.goodmanmfg.com/goodman/info-finder-plus
S
et thermoStat to adjuSt indoor airflow profile
The System offers several custom ON/OFF ramping profiles
for cooling. These profiles may be used to enhance cooling
performance and increase comfort level.
•
Profile A provides only an OFF delay of one (1) minute
at 100% of the cooling demand airflow.
100% CFM
OFF
Cooling Demand
Trim more than 10%
settings are invalid.
Trimmed up CFM
makes miss matching
error.
Trim more than 5%
settings are invalid.
Trimmed up CFM
makes miss matching
error.
S
delay and cool
Select "Cool/Heat Airflow ON Delay" or "Cool/Heat Airflow
OFF Delay". Check the installation manual of the indoor unit
for more details.
It change fan delay for set duration from normal operation.
S
Status menu displays information about the systems current
status.
This menu can be utilized to confirm correct functionality of
the equipment and for troubleshooting purposes
h
It is recommended to set the outdoor temperature lockouts
during the initial thermostat set up. Heat pump lockout temp
will enable the compressor to be turned off and switch heat-
ing source from refrigeration to auxiliary/secondary heating
under low outdoor ambient conditions.
Aux heat lockout temp will enable auxiliary/secondary heating
100% CFM
to be turned off when outdoor temperature is higher than the
OFF
aux heat lockout temp.
1 min
30
•
Profile B ramps up to full cooling demand airflow
by first stepping up to 50% of the full demand for
30 seconds. The motor then ramps to 100% of the
required airflow. A one (1) minute OFF delay at 100%
of the cooling airflow.
100% CFM
50% CFM
OFF
1/2 min
Cooling Demand
Profile C ramps up to 82% of the full cooling demand
•
airflow and operates there for approximately 7 1/2 minutes.
The motor then steps up to the full demand airflow. Profile
C also has a one (1) minute 100% OFF delay.
82% CFM
OFF
7 1/2 min
Cooling Demand
•
Profile D (default) ramps up to 50% of the demand
for 1/2 minute, then ramps to 82% of the full cooling
demand airflow and operates there for approximately
7 1/2 minutes. The motor then steps up to the full
demand airflow. Profile D has a 1/2 minute at 50%
airflow OFF delay.
82% CFM
OFF
50% CFM
1/2 min
7 1/2 min
Cooling Demand
Airflow Tables
et thermoStat to adjuSt cool
/
heat airflow off delay
et thermoStat to check SyStem StatuS
eat pump with outdoor temperature lockoutS
ASXS6S̲3P679063-2D̲ALL̲220729.pdf
100% CFM
1 min
100% CFM
100% CFM
1 min
100% CFM
50% CFM
1/2 min
/
heat airflow on
OFF
OFF
OFF