Descargar Imprimir esta página

Endress+Hauser Proline Cubemass 100 Instrucciones De Seguridad página 10

Publicidad

XA01143D
Temperature
tables
10
• Only use certified cable entries or sealing plugs. The metal sealing
plugs supplied meet this requirement.
• Supplied cable glands M20 × 1.5 are only suitable for fixed
installation of cables and connections. In the installation, a strain
relief must be provided.
• Basic specification, order code for "Housing", option B, C:
To protect the housing of stainless steel housings: Ensure that the
housing gasket is flat and not bent when closing the housing cover.
Replace bent gaskets.
Ex ec type of protection
• Seal unused entry glands with approved sealing plugs that correspond
to the type of protection.
• Only use certified cable entries or sealing plugs.
Optional RFID TAG
• In the case of high electromagnetic field intensities in accordance
with IEC/EN 60079-14: Use is not permitted.
• Avoid electrostatic charging.
Potential equalization
• Integrate the device into the potential equalization .
• If the ground connection has been established via the pipe as
specified, it is also possible to integrate the sensor into the potential
equalization system via the pipe.
Ambient temperature
Minimum ambient temperature:
T
= –40 °C
a
Maximum ambient temperature:
T
= +60 °C depending on the medium temperature and temperature
a
class
Medium temperature
Minimum medium temperature
T
= –50 °C
m
Maximum medium temperature
T
for T6...T1 depending on the maximum ambient temperature T
m
Compact version
Proline Cubemass 100
a
Endress+Hauser

Publicidad

loading