CLEANING AND MAINTENANCE WARNINGS
Turn o the device and disconnect the power before cleaning. Failure to do so can cause
•
electrical shock.
Do not clean the air conditioner with excessive amounts of water.
•
Do not clean the air conditioner with combustible cleaning agents. Combustible cleaning agents
•
can cause re or deformation.
CAUTION
Turn o the air conditioner and disconnect the power if you are not going to use it for a long time.
•
Turn o and unplug the unit during storms.
•
Make sure that water condensation can drain unhindered from the unit.
•
Do not operate the air conditioner with wet hands. This may cause electric shock.
•
Do not use device for any other purpose than its intended use.
•
Do not climb onto or place objects on top of the outdoor unit.
•
Do not allow the air conditioner to operate for long periods of time with doors or windows open,
•
or if the humidity is very high.
ELECTRICAL WARNINGS
Only use the specified power cord. If the power cord is damaged, it must be replaced by the
•
manufacturer
, its service agent or similarly quali ed persons in order to avoid a hazard.
Keep power plug clean. Remove any dust or grime that accumulates on or around the plug. Dirty
•
plugs can cause re or electric shock.
Do not pull power cord to unplug unit. Hold the plug firmly and pull it from the outlet. Pulling
•
directly on the cord can damage it, which can lead to fire or electric shock.
•
Do not modify the length of the power supply cord or use an extension cord to power the unit.
Do not share the electrical outlet with other appliances. Improper or insu cient power supply
•
can cause re or electrical shock.
The product must be properly grounded at the time of installation, or electrical shock may occur.
•
For all electrical work, follow all local and national wiring standards, regulations, and the
•
Installation Manual. Connect cables tightly, and clamp them securely to prevent external forces
from damaging the terminal. Improper electrical connections can overheat and cause re, and may
also cause shock. All electrical connections must be made according to the Electrical Connection
Diagram located on the panels of the indoor and outdoor units.
All wiring must be properly arranged to ensure that the control board cover can close properly. If
•
the control board cover is not closed properly, it can lead to corrosion and cause the connection
points on the terminal to heat up, catch re, or cause electrical shock.
If connecting power to xed wiring, an all-pole disconnection device which has at least 3mm
•
clearances in all poles, and have a leakage current that may exceed 10mA, the residual current
device(RCD) having a rated residual operating current not exceeding 30mA, and disconnection
must be incorporated in the xed wiring in accordance with the wiring rules.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner' s circuit board (PCB) is designed with a fuse to provide overcurrent protection.
The specifications of the fuse are printed on the circuit board ,such as :
T3.15A/250VAC, T5A/250VAC, etc.
T20A/250VAC(<=24000Btu/h units), T30A/250VAC(>24000Btu/h units)
NOTE: For the units with R32 refrigerant , only the blast-proof ceramic fuse can be used.
Page 5