Installation flow sensor (FS)
Mount ball valves up- and down-
stream of the flow sensor.
Consider the correct installa-
tion point. Normally this is in the
return pipe (colder pipe at heating
systems). Note the type plate
information.
Consider the correct flow direction.
This is indicated by an arrow on the
side of the flow sensor.
At C5-CMF type A1, the arrow is
at the bottom of the measuring
capsule.
Install horizontally, horizontally
tipped by 90 ° or vertically only, not
tilted, inclined or overhead. Instal-
lation into horizontal or upstream-
ing or downstreaming pipelines.
Do not install at highest point of
piping to avoid air inside the flow
sensor.
Consider the dimensions of the heat
meter. Axial distance between two
flow sensors at least 135 mm.
Installation of the ball valve for the
temperature sensor
In case of new meter sites install a
ball valve with a thread hole M10x1
for the external temperature sensor.
For C5-CMF type A1 a special ball
valve with temperature sensor con-
nection M12x1.5 (external thread)
is required.
For symmetrical temperature sen-
sor installation, mount an identical
ball valve in the return.