NOTE
If the device is connected, the overvoltage conductors / varistors contained in the device have an impact on
the electrical system insulation resistance test as per HD 60364-6 / IEC 60364-6 Low-voltage installations-
Part 6: Verification.
IEC 60364-6 6.4.3.3 describes two options for this case. The first option is to disconnect devices with an
overvoltage conductor or, if this is not practicable, then the test voltage can be reduced to 250V.
3
Assembly and preparation
3.1
Choosing the installation location
DANGER
Risk of fatal injury due to fire or explosions!
Fire caused by flammable or explosive materials in the vicinity of the device can lead to serious injuries.
Do not mount the inverter in potentially explosive atmospheres or in the vicinity of highly flammable
materials.
CAUTION
Property damage due to gases that have an abrasive effect on surfaces when they come into contact with
ambient humidity caused by weather conditions.
The device housing can be seriously damaged due to gases in combination with air humidity resulting from
weather conditions (e.g. ammonia, sulphur).
If the device is exposed to gases, the installation must be carried out at observable locations.
Perform regular visual inspections.
Immediately remove any moisture from the housing.
Ensure adequate ventilation at the installation location.
Immediately remove dirt, especially on vents.
Failure to observe these warnings may lead to device damage which is not covered by the manufac-
turer warranty.
NOTE
Access by maintenance personnel for service
Any additional costs arising from unfavourable structural or installation conditions will be billed to the cus-
tomer
Installation space
ž
As dry as possible, climate-controlled, the waste heat must be dissipated away from the device.
ž
Unobstructed air circulation.
ž
When installing the device in a control cabinet, provide forced ventilation for sufficient heat dissipation.
ž
Close to the ground, accessible from the front and sides without requiring additional resources.
ž
Protected on all sides against direct weather exposure and sunlight (thermal heating) in outdoor areas. Implement-
ation where necessary via constructional measures, e.g. wind breaks.
Installation surface
ž
Must have adequate load-bearing capacity
ž
Must be accessible for installation and maintenance
ž
Must be made out of heat-resistant material (up to 90 °C )
ž
Must be flame resistant
ž
Minimum clearance during installation: See comprehensive operating instructions under
ergy.com/de/downloads