7 Commissioning
2. Select [Edit parameters].
3. Select the desired parameter group.
☑ All available parameters of the parameter group will be displayed.
4. Set the desired parameters.
5. Select [Save all].
☑ The inverter parameters are set.
7.6
Adjustable Parameters
You can set the following parameters for voltage and frequency monitoring via the user interface of
the inverter (see the inverter user manual for the description of the basic procedure for the change
of operating parameters)
The voltage specifications are based on the line-to-neutral voltages. If the set
values are present as line-to-line voltages, these have to be converted to line-to-
neutral voltages.
Name
Voltage monitoring of upper maximum threshold as
RMS value
Voltage monitoring median maximum threshold
(Overvoltage/Fast)
Voltage monitoring lower maximum threshold
(Overvoltage/Slow)
Voltage monitoring upper minimum threshold (Un-
dervoltage/Slow)
Voltage monitoring of median minimum threshold
(Undervoltage/Fast)
Voltage monitoring of lower minimum threshold as
RMS value
Voltage monitoring of upper max. thresh. as RMS
value for tripping time
Voltage monitoring median max. threshold trip.time
(Overvoltage/Fast, maximum time)
Voltage monitoring lower max. threshold trip. time
(Overvoltage/Slow, maximum time)
Voltage monitoring upper min. threshold trip. time
(Undervoltage/Slow, maximum time)
Voltage monitoring median min. threshold trip.time
(Undervoltage/Fast, maximum time)
56
STP33-62-US-41-IA-xx-14
SMA Solar Technology AG
Value/range
Default value
220 V to 332.4 V
220 V to 332.4 V
220 V to 305 V
103.5 V to 277.0 V
103.5 V to 277.0 V
103.5 V to 277 V
0.05 s to 59 s
0.05 s to 59 s
0.1 s to 60 s
0.1 s to 60 s
0.1 s to 60 s
Installation Manual
332.4 V
332.4 V
304.7 V
243.8 V
138.5 V
138.5 V
0.16 s
0.16 s
1.0 s
2.0 s
0.16 s