Anomalies related to the plumbing circuit
PROBLEM
No increase in
temperature with
stove in operation
PROBLEM
Condensation
in thermostove
Radiators cold
in winter but the
thermostove boils
Hot water in not
provided
The thermostove boils
under "modulation"
that reaches the
temperature set on
the thermostat of the
thermostove
The thermostove goes
into "modulation"
as it reaches the
temperature set on
the thermostat of the
thermostove even
at low temperatures
of the water in the
thermostove
High variability of
domestic hot water
temperature
86
POSSIBLE CAUSE
1. Incorrect combustion
adjustment
2. Thermostove/system dirty
3. Insufficient stove power
POSSIBLE CAUSE
1. Incorrect setting maximum
water temperature in the
thermostove
2. Insufficient fuel consumtion
1. Circulator does not run
because blocked
2. Radiators have air in them
1. Circulator pump blocked
1. It 'been set to a value of
thermostat too high
2. It was set too much power to
the implant.
1. Modify the parameter for the
maximum smoke temperature
modulation to edit
2. Dirty stove: the fumes are too
high temperature.
1. Water flow is too high
REMEDY
1. Check parameters
2. Check and clear the thermostove
3. Check that the stove is properly sized for the
requirements of the system
REMEDY
1. Set the stove to a higher temperature. The
maximum water temperature in the thermostove is
65 ° C and can not be set below 40 ° C or above 80
° C. It is advisable to never adjust the temperature
below 50/55 ° C to avoid condensation in the
thermostove.
Adjust the power of the pump at a higher
temperature to 50/55 ° C.
2. Contact your Authorized Assistance Center
1. Free up the circulator by removing the plug and
turning the shaft with a screwdriver.
Check the electrical connections of the same,
replace if necessary
2. Vent the radiators
1. Free the circulator pump
1. Lower the temperature in the thermostove
2. Reduce the value of operating power
1. Contact your Authorized Assistance Center
2. Clean the tube bundle
1. Reduce the flow of water (4/6 liters per minute)