SYSTEM TYPES
7 basic system types are listed below:
– Heating only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (I1)
– Heating with external hot water tank . . . . . . . . . . . . . . . . . . . . . . (I2)
– Cascade of 2/3 boilers for heating only with zone valves . . . . . . (I3)
– Cascade of 2/3 boilers for heating only with zone pumps . . . . . . (I4)
– Cascade of 2/3 boilers with external hot water tank and zone valves (I5)
– Cascade of 2/3 boilers with external hot water tank and zone pumps (I6)
– Cascade of 2/3 boilers with external hot water tank and 3
zones with mixer valve, pump and floor
A hydraulic diagram, wiring diagram and table of configuration para-
meters is provided for each of these below, in which the parameters
to be changed with respect to factory settings are identified. The
complete list of parameters provided in sections 10, 11 and 12 may
be used to restore starting conditions if parameters are changed
unintentionally. Once you have selected the type of system, all you
have to do is enter the parameters appearing in the corresponding
table in the controller and perform tests on outputs and inputs to
check that all connected components have been identified correctly
(this is recommended).
3. 1
PRELIMINARY OPERATIONS
1) REMOVE THE JUMPERS FROM THE TERMINAL IN THE BOI-
LER'S ELECTRICAL PANEL (REFER TO THE BOILER WIRING
DIAGRAM)
2) TO ENSURE CORRECT FUNCTIONING OF THE DEVICE, SET THE
BOILER CONTROL THERMOSTAT TO THE MAXIMUM SETTING
3.3. 1
SYSTEM I1 – heating only boiler
Hydraulic circuit
SE
84
system.
. . . . . . . . . . . . . . . (I7)
SC
RVA
43.222
BOILER
CALDAIA
3.2
CABLE LENGTH
Maximum lengths for cables used to connect Albatros RVA43.222
(LPB bus) units with one another and with their probes are shown in
the table below in relation to cable section.
Cable type
LPB
Copper – 1,5 mm
Permanent sensors
ø 0,6 mm
Permanent sensors
1,0 mm
2
0
Permanent sensors
1,5 mm
2
3.3
SYSTEM I1: HEATING ONLY
The features of this type of system are summed up below:
– Automatic Summer/Winter switchover.
– Climate control with outdoor probe.
– Boiler works only on demand from room thermostat.
– Minimum boiler temperature is maintained.
– Anti-condensation protection on the basis of return temperature.
– Weekly heating programming.
The components included in the boiler kit to be purchased are as fol-
lows (the QAC31 outdoor temperature probe is sold separately):
Code
Description
RVA43.222
Control unit
QAZ21 (immersion)
– Burner delivery probe
LEGEND
TA
SC
SE
PI
TA
PBY
TM
PBY
TM
Max. length
2
bipolar
250 m
20 m
80 m
120 m
Quantity
Room thermostat
Boiler delivery probe (QAZ21)
Outdoor temperature probe (QAC31)
Boiler pump
Bypass pump
Minimum return thermostat
PI
M
R
1
1