Cable Specifications
No.
Terminal/Port
1
PV input terminal
Dry contact
2
communication
terminal
3
CT communication
terminal
Remote Shutdown
4
communication
terminal
Power supply
5
terminal for RSD
module
Meter
6
communication
terminal
Communication
7
terminal for multi
inverter parallel
connection
8
USB port
9
AC cable terminal
10
Grouding busbar
|
Especificaciones de los cables
Silkscreen
PV1+ PV1-
PV2+ PV2-
PV3+ PV3- (Only for
GW7700-MS-US30,
GW9600-MS-US30,
GW11K4-MS-US30)
DRY-OUT
CT2
CT1
DRM0
RSD-12V
METER
485-1
485-2
USB
GRID-L1
GRLD-N
GRID-L2
-
Recommended Cable Specifications
90℃(194°F) copper cables, 12AWG.
-
-
Outdoors communication cables that meet
UL2919, CM/CMG(NEC type), or CMH(CSA type)
requirements, 24-16AWG.
Outdoors communication cables that meet
UL2919, CM/CMG(NEC type), or CMH(CSA type)
requirements, 24-16AWG.
Outdoors communication cables that meet
UL2919, CM/CMG(NEC type), or CMH(CSA type)
requirements, 24-16AWG.
Outdoors communication cables that meet
UL2919, CM/CMG(NEC type), or CMH(CSA type)
requirements, 24-16AWG.
-
90℃(194°F) copper cables, 6AWG.
90℃(194°F) copper cables, 10-6AWG.