Descargar Imprimir esta página

Mennekes AMTRON Compact 2.0 7,4 Manual De Instrucciones Y De Instalación página 49

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 57
Electrical connection of the switching contact
ATTENTION
Material damage due to improper installation
Improper installation of the switching contact can
damage the product or lead to malfunctions. Ob-
serve the following requirements during the install-
ation:
u Select suitable cable routing to avoid interfer-
ence.
Enable input
12 V DC, 8 mA
Fig. 13: Schematic circuit diagram: Connection of an
external switching contact
u Install external switching contact.
u Strip the cable.
u Strip the conductors 10 mm.
u Connect the conductors to terminals 1 and 2
(XG1).
u Comply with the connection data for the enable
input.
1 "4 Technical data" [} 9]
Configuration
u Set DIP switch 3 on bank S1 to "ON".
If a switching contact with pulse signal has been in-
stalled, an additional setting is required in the con-
figuration tool.
1 "6.5 Description of the configuration tool"
[} 19]
6.3
Switching on the product
The tasks described in this section may only
be carried out by a qualified electrician.
Requirement(s):
XG1
1
NO
2
ü Product is installed correctly.
ü Product is not damaged.
ü The necessary protective devices are installed
in the upstream electrical installation in compli-
ance with the relevant national regulations.
1 "5.2.2 Protective devices" [} 12]
ü During the initial setting-up process, the product
was inspected in accordance with IEC 60364-6
and the applicable national regulations (e.g. in
Germany: DIN VDE 0100-600).
1 "6.4 Testing the product" [} 19]
u Switch on the power supply and check.
6.4
Testing the product
The tasks described in this section may only
be carried out by a qualified electrician.
u At initial start-up, test the product in accordance
with IEC 60364-6 and the applicable national
regulations (e.g. in Germany: DIN VDE
0100-600).
The test can be carried out in conjunction with the
MENNEKES test box and standard-compliant test
equipment. The MENNEKES test box simulates
vehicle communication. Test boxes are available as
an accessory from MENNEKES.
6.5
Description of the configuration tool
The basic settings can be made via DIP switches at
the charging station. The configuration tool is re-
quired for advanced settings.
On initial commissioning, on our website
under "Services" > "Software updates",
check whether there is a newer firmware
version of the product or configuration tool.
Update if necessary.
1 "8.3 Firmware update" [
EN
 23]
}
19

Publicidad

loading