Component
Maintenance work
Electrical system u Inspection of the electrical
system in accordance with
IEC 60364-6 and the re-
spective applicable national
regulations (e.g. DIN VDE
0105-100 in Germany).
u Repetition of measurements
and tests according to IEC
60364-6 and the applicable
national regulations (e.g. in
Germany: DIN VDE
0105-100).
u Carry out a functional test
and charging simulation (e.g.
using a MENNEKES test box
and standard-compliant test
equipment).
u Properly eliminate damage to the product.
u Document maintenance.
You can find the MENNEKES maintenance log
on our website under "Services" > "Documents
for installers".
1 "1.1 Website" [} 2]
8.2
Cleaning
DANGER
Risk of electric shock due to improper cleaning
The product contains electrical components that
carry high voltage. In case of improper cleaning,
people can be seriously injured or killed due to
electric shock.
u Clean only the outside of the housing.
u Do not use running water.
ATTENTION
Material damage due to improper cleaning
Improper cleaning can damage the housing.
u Wipe the housing with a dry cloth or a cloth
lightly moistened with water or spirit (94 % vol.).
u Do not use running water.
u Do not use high-pressure cleaning devices.
8.3
Firmware update
The current firmware is available on our
website under "Services" > "Software up-
dates".
1 "1.1 Website" [
The configuration tool is required to perform a firm-
ware update.
1 "6.5 Description of the configuration tool" [} 19]
 2]
}