MicroLogix™ 1100 Programmable Controllers
Output Specifications
General
Description
Relay and FET Outputs
Maximum Controlled Load
Maximum Continuous Current:
Current per Group Common
Current per Controller
Relay Outputs
Turn On Time/Turn Off Time
Load Current
(1)
5A for UL 508
3A for UL 1604, Class 1, Division 2, Hazardous Locations, Groups A, B, C, D
(2)
scan time dependent
Relay Contact Ratings
Maximum Volts
240V ac
120V ac
125V dc
24V dc
(1)
For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied dc voltage. For example, 28 VA/48V dc = 0.58A. For dc voltage applications less than 14V, the make/break ratings
for relay contacts cannot exceed 2A.
(2)
5.0A for UL 508
3.0A for UL 1604, Class 1, Division 2, Hazardous Locations, Groups A, B, C, D
(3)
3.0A above 40°C.
Publication 1763-IN001A-MU-P - May 2005
1763
-L16AWA, -L16BWA
1440 VA
(1)
5A/3A
at 150V max
For UL 508, 30A or total of per-point loads, whichever is less
For UL 1604, 18A or total of per-point loads, whichever is less
at 240V max
For UL 508, 20A or total of per-point loads, whichever is less
For UL 1604, 18A or total of per-point loads, whichever is less
10 msec (maximum)
10 mA (minimum)
Amperes
Make
Break
15.0A
1.5A
30.0A
3.0A
(1)
0.22A
(1)
1.2A
-L16BBB
1440 VA
5A/3A
(2)
Amperes
Volt-Amperes
(2)
Continuous
Make
(3)
3600 VA
5.0A
/3.0A
(3)
3600 VA
5.0A
/3.0A
1.0A
2.0A
Break
360 VA
360 VA
28 VA

Publicidad

loading

Este manual también es adecuado para:

1763-l16awa1763-l16bwa1763-l16bbb