Description
Power Supply Input to
Backplane Isolation
Input Group to Backplane
Isolation and Input Group to
Input Group Isolation
Output Group to Backplane
Isolation
Output Group to Output
Group Isolation
Description
Input Group to Backplane
Isolation and Input Group to
Input Group Isolation
FET Output Group to
Backplane Isolation
Relay Output Group to
Backplane Isolation
Relay Output Group to Relay
Output Group and FET
Output Group Isolation
MicroLogix™ 1100 Programmable Controllers
1763-L16BWA
Verified by one of the following dielectric tests:1836V ac for 1 second or 2596V
dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests: 1100V ac for 1 second or
1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation).
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2
reinforced insulation)
1763-L16BBB
Verified by one of the following dielectric tests: 1100V ac for 1 second or
1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests: 1100V ac for 1 second or
1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (basic insulation), 150V Working Voltage
(IEC Class 2 reinforced insulation)