6
Cross References
Airflow (cfm)
ATMO 150H
ATMO 150E
ATMO 200H
TM
TM
TM
1 Reduced
20 min/hr
22 cfm
23 cfm
22 cfm
1 Reduced
40 min/hr
43 cfm
47 cfm
44 cfm
Exchange
Reduced
65 cfm
70 cfm
66 cfm
Fan Speed
Medium
Selection
118 cfm
125 cfm
128 cfm
Normal
191 cfm
190 cfm
233 cfm
Power (W)
ATMO 150H
ATMO 150E
ATMO 200H
TM
1 Reduced
TM
TM
20 min/hr
23 W
23 W
23 W
1 Reduced
43 W
43 W
43 W
40 min/hr
Exchange
Reduced
62 W
62 W
62 W
Fan Speed
Medium
Selection
92 W
92 W
92 W
Normal
145 W
145 W
145 W
Reduced 20 min/hr & 40min/hr cyclical operation are average equivalent values. Values from each table are typical for a
duct design with 0.4-inch external static pressure. The airfl ow/power values in the cross-reference table can be
adjusted by percentage based on actual installed airfl ows.
Troubleshooting
LED is OFF on the FID
Maintenance
The FID Module and Control require no maintenance. For HRV/ERV maintenance, refer to the included HRV/ERV Installation and Op-
eration Manual.
Warranty
The FID Module has a full 5 year warranty and the FID indicator panel has a full 2 year warranty.
fantech
ATMO 200E
HERO 120H
HERO 150H
HERO 200H
HERO 150H-EC
TM
R
R
R
R
24 cfm
24 cfm
26 cfm
33 cfm
26 cfm
48 cfm
49 cfm
51 cfm
66 cfm
53 cfm
72 cfm
73 cfm
77 cfm
99 cfm
79 cfm
143 cfm
106 cfm
109 cfm
155 cfm
116 cfm
233 cfm
127 cfm
180 cfm
234 cfm
194 cfm
ATMO 200E
HERO 120H
HERO 150H
HERO 200H
HERO 150H-EC
HERO 250H-EC
TM
R
R
R
R
23 W
22 W
24 W
29 W
10 W
43 W
44 W
48 W
59 W
20 W
62 W
66 W
72 W
88 W
30 W
92 W
116 W
92 W
135 W
45 W
145 W
166 W
170 W
210 W
110 W
• Ventilation mode may be set to OFF/Standby.
• Recirculation mode may be selected.
• Defrost mode may be triggered if outdoor temperatures are
below -5°C (23°F). Wait 10 minutes and check LED status.
• If the LED is still OFF, check pressure tubes are properly
inserted into the door pressure taps.
• Check fi lters.
• Check that outdoor terminal supply or exhaust hoods are not
blocked.
• If problem persists, tell a service technician.
HERO 250H-EC
R
27 cfm
53 cfm
KIT de cumplimiento de FID
80 cfm
152 cfm
Sistema de visualización de las indicaciones de avería
275 cfm
ESTE PRODUCTO REQUIERE 2 PAQUETES
463988 Equipo de preparación para la instalación
464000 Juego de acabados
R
13 W
27 W
40 W
100 W
260 W
Estados Unidos
Lenexa, KS, 66215
Tel.: 800.747.1762
Canadá
Bouctouche, NB, E4S 3M5
Tel.: 800.565.3548
Fantech se reserva el derecho de modificar, en cualquier momento y sin previo aviso, todas o cualquiera de las características, diseños,
componentes y especificaciones de sus productos con el fin de mantener su posición de liderazgo tecnológico.
Visite nuestro sitio web www.fantech.net para obtener información técnica más detallada.
Manual de instalación y funcionamiento
Artículo n.º: 445811
Fecha de rev.: 24-08-2022