Parámetros 200: Unidad básica
Parámetro
Modo de funcionamiento del quemador (canal
de combustible modulante / multietapa, accio-
namientos...)
__=indefinido (borrar curvas)
1 =G mod
2 =Gp1 mod
3 =Gp2 mod
201
4 =Lo mod
5 =Lo 2 etapas
6 =Lo 3 etapas
7 =G mod pneu
8 =Gp1 mod pneu
9 =Gp2 mod pneu
10 =LoGp mod
11 =LoGp 2 etapas
12 =Lo mod 2 válvulas de combustible
13 =LoGp mod 2 válvulas de combustible
14 =G mod pneu sin accionamiento
Description
Burner operating mode (fuel train, modula-
ting / multistage, actuators, etc..)
__= undefined (delete curves)
1 = gas direct ignition (G mod)
2 = ignition by gas pilot connected between
the two gas solenoid valves EV1/EV2 (Gp1
mod)
3 = ignition by gas pilot connected upstream
the gas EV1 (Gp2 mod)
4 = light oil ignition - modulating (Lo mod)
5 = light oil ignition - double stage (Lo 2 stage)
6 = light oil ignition - three stage (Lo 3 stage)
7 = gas direct ignition - pneumatic regulation
(G mod pneu)
8 = ignition by gas pilot connected between
the two gas solenoid valves EV1/EV2 - pneu-
matic regulation (Gp1 mod pneu)
9 = ignition by gas pilot connected upstream
the gas EV1 - pneumatic regulation (Gp2 mod
pneu)
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator