12. INITIAL IGNITION - SPECIAL FUNCTIONS
When the boiler is powered up, the code "311" appears on the display and the boiler is ready for "initial ignition".
Follow the procedure "GAS EXTRACTION FUNCTION" as described in the section below and enable programme 312.
After this operation, the boiler is ready to ignite the burner.
During this phase it is recommended to keep the pressure in the system at a value between 1 and 1.5 bar.
12.1 SYSTEM GAS EXTRACTION FUNCTION
This function is used to facilitate the elimination of the air inside the heating circuit when the boiler is first installed or after
maintenance when the water is drained from the primary circuit.
together for 6 seconds. When the function is active, On
To enable the system gas extraction function press buttons
appears on the display for a few seconds, followed by programme row 312.
The electronic board will activate a pump on/off cycle lasting 10 minutes. The function will automatically stop at the end of the
cycle. To manually exit this function, press the above buttons together for 6 seconds once again.
12.2 CALIBRATION FUNCTION
To calibrate the gas valve, proceed as follows:
• Press buttons
and
together for at least 6 seconds. When the function is enabled, the displays shows "On" for a few
seconds followed by programme row "304" alternated with the % of boiler power.
• Press
to gradually adjust power (sensitivity 1%).
• To exit press both buttons together for at least 6 seconds, as described in point one
Press
to display the instantaneous flow temperature for 15 seconds.
12.3 CHIMNEY SWEEPER
When this function is enabled, the boiler generates maximum heating power. To enable the function, proceed as follows:
• press
together for 6 seconds. The display shows "303" alternated with the power output of the boiler.
• Press
and
to adjust boiler power 1=minimum, 2=maximum DHW, 3=maximum heating.
• To interrupt the function repeat the procedure described in point one.
13. FAULTS THAT CANNOT BE RESET BY THE USER
In case of FAULTS that cannot be reset by pressing
(such as E151 or exceeding 5 manual
RESET attempts by the user) RESET the board by pressing the black button ( R) located
under the rubber cap (symbol
) of the front control panel (figure to side).