Descargar Imprimir esta página

Baxi Luna Duo-Tec MP+ 1.110 Manual De Uso Destinado Al Usuario Y Al Instalador página 40

Ocultar thumbs Ver también para Luna Duo-Tec MP+ 1.110:

Publicidad

Idiomas disponibles

Idiomas disponibles

CONFIGURATION
P40
5700
Not used (Do NOT change this parameter)
P41
5710
Zone 1 heating circuit (1=enabled)
P42
5715
Zone 2 heating circuit (1=enabled)
P43
5730
DHW sensor (1=Tank sensor, 2=Thermostat, 3=instantaneous sensor)
P44
5890
Not used (Do NOT change this parameter)
P45
5931
*BX2 sensor input (first auxiliary sensor – section 11)
P46
5932
*BX3 sensor input (second auxiliary sensor – section 11)
P47
5977
*Input H5 (multifunction input – 18=Room thermostat)
P48
6020
*Configuration of accessory Expansion Unit
P49
6024
Input EX21 module 1 (configuration of HC Safety Thermostat)
P50
6046
Input H2 module 1 (multifunction input)
P51
6097 Sensor type collector (1= NTC, 2= Pt 1000)
P52
6110 Building time constant (depending on the insulations of the building)
P53
6220 Software version
P54
6600 LPB device address (BUS connection)
P55
6601 LPB segment address (BUS connection)
P56
6640 Clock time source
MAINTENANCE
P57
7045 Time after maintenance
P58
6704 View/Hide secondary fault internal code (0=no)
BURNER CONTROL
P59
9512 Required ignition speed
P60
9524 Required minimum operating speed
P61
9529 Required maximum operating speed (high speed)
BOILER CONTROL PANEL PARAMETERS
P62
-
Unit of measurement (1=bar, °C – 2=PSI, °F)
P63
-
Control panel operation: (1=central, 0=local)
P64
-
Software version
* see "Accessories not included in supply"
xx: the value depends on the software version
(a): parameters read on the front boiler panel (fixed control panel)
15. GAS VALVE CALIBRATION
To calibrate the gas valve, enable the calibration function as described in section 12.2 and carry
out the following operations:
1) Calibrating MAXIMUM heat output.
Check that the
/O
measured on the flue duct, with the boiler operating at maximum heat
2
capacity, matches that indicated in table 1C. If it does not, turn the adjustment screw (V) on the
gas valve. Turn the screw clockwise to decrease the level of
2) Calibrating REDUCED heat output
Check that the
/O
measured on the flue duct, with the boiler operating at minimum heat
2
capacity, matches that indicated in table 1C. If it does not, remove the threaded brass cap on the
gas valve and turn the adjustment screw (K). Turn the screw clockwise to increase the level of
and anticlockwise to decrease it.
V
Gas flow adjustment screw
PI
Pressure signal sealed chamber
For each CO2/O2 value found at the maximum thermal capacity, there is a range of CO2/O2 values at the minimum thermal
capacity shown in the same line of the table.
The nominal calibration values of the gas valve for each type of gas used are shown in bold.
The CO2/O2 values are with the cover closed.
The maximum permitted CO value must be lower than 250 ppm.
TABLE 1C
G20 (1.90)
CO
(%)
O
2
P max
P min
P max
9,5
8,8÷9,2
3,9
9,4
8,7÷9,1
4,1
9,3
8,6÷9
4,3
9,2
8,5÷8,9
4,5
9,1
8,4÷8,8
4,7
9
8,3÷8,7
4,8
8,9
8,2÷8,6
5
8,8
8,1÷8,5
5,2
8,7
8÷8,4
5,4
8,6
7,9÷8,3
5,6
8,5
7,8÷8,2
5,7
7221409.03 (2-07/16)
(low speed)
xxx : the value depends on the type of boiler
K
OFFSET adjustment screw
Pi
Gas supply pressure tap
G31 (1.90)
(%)
CO
(%)
2
2
P min
P max
P min
4,5÷5,2
10,5
10÷10,4
4,7÷5,4
10,4
9,9÷10,3
4,8÷5,6
10,3
9,8÷10,2
5÷5,7
10,2
9,7÷10,1
5,2÷5,9
10,1
9,6÷10
5,4÷6,1
10
9,5÷9,9
5,6÷6,3
9,9
9,4÷9,8
5,7÷6,5
9,8
9,3÷9,7
5,9÷6,6
9,7
9,2÷9,6
6,1÷6,8
9,6
9,1÷9,5
6,3÷7
9,5
9÷9,4
month
rpm
rpm
rpm
(b): parameters read on the Remote Control
and anti-clockwise to increase it.
O
(%)
2
P max
P min
4,9
5,1÷5,7
5,1
5,2÷5,8
5,2
5,4÷6
5,4
5,5÷6,1
5,5
5,7÷6,3
5,7
5,8÷6,4
5,8
6÷6,6
6,0
6,1÷6,7
6,1
6,3÷6,9
6,3
6,4÷7,1
6,4
6,6÷7,2
40
---
-
---
-
1
0
-
0
0
1
1
-
33
0
-
0
0
-
0
0
-
18
0
-
0
0
-
0
0
-
0
0
-
2
1
h
15
0
-
---
0
-
1
-
0
-
0
xxx
0
-
1
0
xxx
0
xxx
0
xxx
0
-
1
1
-
1
0
-
xx
0
---
1
1
3
43
19
19
32
7
1
58
2
50
99
16
14
3
240
1
8000
8000
8000
2
1
999

Publicidad

loading

Este manual también es adecuado para:

Luna duo-tec mp+ 1.90