RED and
GREEN buttons to scroll through the list until the desired valve serial number is highlighted . Then
Use the
press the ■ SET button to assign the selected valve .
Note: The Navigator Pro cannot be assigned to more than one valve. The Navigator Pro will remember its as-
signed valve even when the power is off.
Once the Navigator Pro has been successfully assigned to a valve, the screen will proceed to the main operational
screen . The Navigator Pro can now be used to open and close the valve . However, valve calibration must be performed
in order to display valve position properly .
6.2 CALIBRATING VALVE POSITION
Menu location: Setup Menu → OEM Configuration → Valve Setup → Valve Calibration
The valve must be calibrated to ensure the position of the valve is accurate . Navigate to the Valve Calibration screen (for
details on accessing this screen and navigating the menu, see "MENU NAVIGATION" in Section 7 below) . The screen
will display the following warning: "The valve will fully open and close during calibration ." After you have verified that
the valve is properly installed to the motor, and there is no danger of damage due to water in the line, press ■ START to
begin the calibration process .
The valve will fully open and close twice to calibrate the valve position sensor . After calibration is complete, press the
■ OK button to return to the Valve Setup screen .
6.3 SETTING PIPE DIAMETER
Menu location: Setup Menu → OEM Configuration → Flow Setup → Flow Options
Valve Serial
Number location
2-23/32"
Valve Serial number location
9-7/8"
Page 10