7.2 Presets
Menu location: Setup Menu → Presets
The Style 9335 Navigator Pro is capable of storing up to three valve positions . These are referred to as "Presets" . Once
stored, the user can quickly revert the valve back to a saved position from the main screen . There are two ways to set
the preset valve positions . They can be set either on the main operation screen or in the Presets Menu . The menu op-
tions are as follows:
• Number of Presets
• Preset Valve Positions
Number of Presets: The Navigator Pro system can be set to have 0, 1, 2 or 3 presets active . To adjust the number of
presets, follow these steps:
1 . Navigate to the Presets menu
2 . Use the
RED or
3 . Press the ■ SET button to save the value .
Preset Valve Positions: The preset valve positions can be set in 5 percent increments from 0% to 100% . These positions
can be set on the main operational screen or in the Presets Menu . To store the preset valve positions, follow one of the
following setup procedures:
To set from the Presets Menu:
1 . Navigate to the Presets Menu
2 . Press the ■ NEXT button so the value under "P1" is highlighted
RED or
3 . Use the
4 . Press the ■ SET button to save the value
5 . Repeat steps 3-4 to set the remaining preset positions, or press the ■ NEXT button to skip to the next value .
To set from the main screen during normal operation:
1 . Adjust the valve to the desired position
2 . Press the = PRESET button until the desired preset is highlighted
3 . Press and hold the = NEXT button until its label changes to "SET" and blinks for 5 seconds . When it stops
blinking, release the button and the new preset position is saved .
4 . Repeat steps 1-3 to set other active presets .
After the desired presets are configured, the operator can easily send the valve to a preset position during normal
operation . Simply press the = PRESET button until the desired preset is highlighted, and then press the ■ GOTO button .
7.3 Diagnostics
Menu location: Setup Menu
The Diagnostics screen contains information that can be useful for troubleshooting the system in the event of a
malfunction . It is intended to be viewed for informational purposes only; there are no user configurable options on this
screen . The Diagnostics screen contains the following information:
• Pressure sensor raw voltage (VDC) . This is the value that the valve controller is reading from the pressure
sensor . Voltage increases as pressure increases . Normal range is 0 .5 to 5VDC .
Note: If no pressure sensor is installed, this value reads 5VDC .
• Flow sensor raw frequency value (Hz) . This is the value sent to the valve controller from the flow sensor . The
value is in hertz and increases as flow increases . Normal range varies based on pipe diameter, but is
typically about 0 to 250Hz .
• Position Sensor value (degrees) . This is the reading from the magnetic sensor in the valve trunion . It is
displayed in degrees and increases as the valve closes . Normal range varies based on installation, but typically
shows a difference of 94 degrees from fully closed to fully open .
• Motor current (amps) . This is the actual operating current of the motor .
Each of these values is updated as the pressure, flow or valve position changes . When finished viewing, press the
■ EXIT button to return to the main menu .
GREEN button to select the desired number of presets
GREEN button to set the desired valve position for the first preset
Diagnostics
Page 13