7 Commissioning
Name
Description
dS_1 Network defrost synchronised
for secondary unit controller 1.
▪ 0:
No
synchronisation
performed.
▪ 1: Only at start.
▪ 2: Start & stop.
dS_2 Network defrost synchronised
for secondary unit controller 2.
dS_3 Network defrost synchronised
for secondary unit controller 3.
dS_4 Network defrost synchronised
for secondary unit controller 4
d2
Network end defrost
synchronised for primary unit
controller.
Local defrosting on a LMSEY unit is still possible in two ways:
▪ Manually (from app, supervisory system or user interface).
▪ With parameter "dI" (maximum interval between consecutive
defrosts) taking control. This will happen when a network
connection fault occurs that lasts longer than the "dI" parameter
setting. Therefore the "dI" parameter must always be set.
6.6
About the alarms
To check and reset alarms (error codes), see the operation manual.
7
Commissioning
CAUTION
Preliminary electrical system checks such as earth
continuity, polarity, resistance to earth and short circuit
must be carried out by using a suitable test meter by a
competent person.
WARNING
ONLY qualified persons should conduct commissioning.
Final checks for correct installation
Check that there is no air gap between unit and cold room
wall.
Check the labels of the wires connected to the door micro
switch and the door heater. The door heater wire is a live
wire, while the micro switch wire is a signal wire.
Swapping the wires will cause serious damage to the unit.
Check that all covers are closed correctly.
Check that the electrical wiring of the door micro switch,
door heater and cold room lamp are properly fixed to the
cold room panels.
Check that all the electrical wiring work is correctly
connected.
Check that all cable glands are properly tightened.
DANGER
   
Tripping over loose wiring can tear it loose and cause
electrocution and fire.
Installation manual
26
Final checks for correct setup
Default
Min.
Max.
0
0
2
0
0
2
0
0
2
Test run
0
0
2
0
0
1
8
Once the test run is finished and the unit operates properly, make
sure the following is clear for the user:
▪ Make sure that the user has the printed documentation and ask
▪ Explain the user how to properly operate the system and what to
Check that the programming logic is suitable to control the
unit and the system in question.
Check that the time has been set on the controller.
Check that the time bands have been set correctly.
Check that the standard display (showing the setpoint)
has been set on the user terminal.
Check that the appropriate unit of measure has been set
for the temperature probes (°C or °F).
Connect the unit's electrical plug to the mains outlet.
Turn on the unit.
Set the cold room temperature.
Check that the setpoint of the cold room temperature is
reached.
Start defrost mode.
Check for water leaks.
Check that no alarms occur on the user interface (see
user manual).
Switch off the unit.
WARNING
   
▪ NEVER
directly
touch
refrigerant. This could result in severe wounds caused
by frostbite.
▪ Do NOT touch the refrigerant pipes during and
immediately after operation as the refrigerant pipes
may be hot or cold, depending on the condition of the
refrigerant flowing through the refrigerant piping,
compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the
refrigerant pipes. To avoid injury, give the pipes time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.
NOTICE
At the end of the commissioning procedure, the alarm log
can be reset (if necessary) via the Daikin Installer app.
Hand-over to the user
him/her to keep it for future reference. Inform the user that he can
find the complete documentation at the URL mentioned earlier in
this manual.
do in case of problems.
any
accidental
leaking
LMSEY1A09/13 + LMSEY2A19/25
Daikin LMS
4P728170-1B – 2023.07